48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 1—General Information

 

 

Ground-Fault Protection

Figure 10: Ground-Fault Protection Switches

Micrologic 6.0A Trip Unit

Equipment ground-fault protection protects conductors against overheating and faults from ground-fault currents (￿￿1200 A).

Equipment ground-fault protection is

standard on 6.0A trip units.

Ground-fault pickup (Ig) (A) sets ground

current level where circuit breaker will trip

after the preset time delay.

Ground-fault delay (tg) (B) sets the length of

time that the circuit breaker will carry a

ground-fault current above the ground-fault

pickup current level before tripping.

A

B

06133351

 

 

long time

 

 

 

 

 

 

 

Ir

.8

 

 

tr

 

8

 

 

 

.7

.9

 

(s) 4

12

 

 

.6

 

 

.95

2

 

 

16

 

 

.5

 

 

.98

1

 

 

20

 

 

.4 x In 1

.5 @ 6 Ir24

 

 

 

 

 

short time

 

 

 

 

 

 

Isd

4

 

 

tsd

.4

.4 .3

 

3

5

 

(s)

 

 

 

.3

 

 

.2

 

2.5

 

 

6

 

 

 

 

2

 

 

8

 

.2

 

 

.1

 

 

1.5 x Ir

10

 

.1

 

0

 

 

 

on I2t off

 

 

 

setting

 

delay

 

 

 

Ig

E

 

 

tg

.4

.4 .3

 

 

D

F

(s)

 

 

.3

 

 

.2

 

 

C

 

G

 

 

 

 

 

 

 

H

.2

 

 

.1

 

 

A

 

J

.1

I2t

0

 

 

 

on

off

 

fault

alarm

instantaneous

I i

8

5 10

4 12

315

2off

x In

test

ENGLISH

Equipment ground-fault protection can be

zone-selective interlocked (ZSI) with

upstream or downstream circuit breakers.

Setting the ground-fault delay (tg) to the 0

setting turns off zone-selective interlocking.

Neutral protection and equipment ground-

fault protection are independent and can

operate concurrently.

Table 4:

Micrologic Trip Unit Ground-Fault Pickup Values

 

Ig (= In x....)

 

A

B

C

D

E

F

G

H

J

 

 

 

 

 

 

 

 

 

 

 

In ￿ 400 A

 

0.3

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

 

 

 

 

 

 

 

 

 

 

400 A < In ￿ 1200 A

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

 

 

 

 

 

 

 

 

 

 

 

In > 1200 A

 

500 A

640 A

720 A

800 A

880 A

960 A

1040 A

1120 A

1200 A

 

 

 

 

 

 

 

 

 

 

In = sensor rating.

 

 

 

 

 

 

 

 

 

Ig = ground-fault pickup.

Table 5:

Micrologic Trip Unit Ground-Fault Delay Values

Setting

 

Ground-Fault Delay

 

 

 

 

 

 

 

 

 

I2t off (ms at In) (seconds)

0

0.1

0.2

0.3

0.4

 

I2t on (ms at In) (seconds)

0.1

0.2

0.3

0.4

 

tsd (min. trip) (milliseconds)

20

80

140

230

350

 

 

 

 

 

 

 

 

tsd (max. trip) (milliseconds)

80

140

200

320

500

 

 

 

 

 

 

 

 

 

NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is not recommended as the delay in the upstream device receiving a restraint signal could result in the trip unit tripping in a time shorter than the published trip curve.

Indicator Lights

Overload Indicator Light

Figure 11: Overload Indicator Light

The overload indicator light (A) lights when the Ir long-time pickup level has been exceeded (over 100% on the bar graph).

06133352

 

 

 

long time

 

 

 

 

 

 

 

Ir

.8

 

 

tr

8 12

 

 

.7

.9

 

(s) 4

 

 

.6

 

 

.95

2

 

16

 

 

.5

 

 

.98

1

 

20

 

 

 

.4 x In 1

.5 @ 6 Ir24

 

 

 

 

 

 

 

short time

 

 

 

 

 

 

Isd

 

 

 

tsd

 

.4 .3

 

 

3

4

5

 

.4

 

 

2.5

 

 

6

 

.3

 

.2

 

 

2

 

 

8

 

.2

 

.1

 

 

 

1.5 x Ir

10

 

.1

0

 

 

 

 

on

I2t

 

 

 

 

 

 

 

 

setting

 

delay

 

 

 

IΔn

 

 

ΔI

 

 

 

 

(A) 3

5

7 (ms)230

350

 

2

 

 

10

140

 

 

 

1

 

 

20

 

 

 

 

 

 

 

 

 

.5

 

30

 

60

800

 

alarm

instantaneous

I i

4

 

3

5

 

2.5

 

6

2

 

8

1.510

x In

test

A

100%

40 %

earth leakage

© 1999–2012 Schneider Electric All Rights Reserved

13-EN

Page 15
Image 15
Schneider Electric 5.0A, 3.0A, 2.0A, and 6.0A manual Indicator Lights, Ground-Fault Protection, Overload Indicator Light