2 Insert the extension cord plug into The receptacle.

In case of DGW310DMC, insert either A or B to be remote controlled.

3 Insert the plug into the receptacle of extension cord reel. You can use 3 reels in series (30mx3)

Caution

Never connecta remote control box plug to a receptacle of extension reel connected to AC100/110 Output receptacle in the equipment. The abnormality lamp in the box turns ON to show abnormality when it is connected by mistake.

Never connect any device to a receptacle in the extension reel other than a remote controller. In case of using the cord reel incorporating ELCB set the ELCB ON and use.

5-6. ELCB and Grounding

Danger: Electric Shock

Ground every grounding terminal to the earth as set in the manual. If even one of all is unconnected by mistake or accident, it will make much more dangerous for human than the NO RELAY case, because leaking current inevitably goes through the body.

Even though all the terminals of the loads have been grounded to the earth, the bonnet grounding thermal should be grounded to the earth.

Grounding should be made after the engine stopped.

Whenever the ELCB relay has activated, you should repair the leaking part always first of all.

Caution

 

 

 

 

 

The ELCB activates only for AC output.

 

 

 

ELCB activates when AC output is used with the output selector switch at ECO

position for protection

 

load damage.

 

 

 

The circuit breaker is incorporated with ELCB to protect electric shock

The breaker trips when current leakage is detected due to insufficient insulation of loads The specifications of ELCB are as follows.

Rated Sensitive Current less than 30mA (Grounding Resistance less than 500 )

Activation Time

less than 0.1 second

13