5.How to operate EX500 - GDN1 ( DeviceNet )

5-1. Connection style

DeviceNet unit can be connected by T branch, Multi branch and Branch line branch.

Total extension length of trunk and stay is different depending on communication speed and thickness of communication cable.

EX500 series can be connected only by T branch.

Terminating resistance

Multi branch

T branch

Main

Terminating resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multi branch

Branch line

Node

Node

Branch line

Branch line branch

Max. 6m

Node

Multi

branch

Node

 

Node

 

 

 

Node

Node

Branch line

Node

Node

Wiring length

 

 

Communication speed ( k bit / sec. )

 

 

125

250

500

Max. length

Thick cable

500m or less

250m or less

100m or less

of

Thin cable

 

100m or less

 

Network

 

 

 

 

 

 

Total length of branch line

156m or less

78m or less

39m or less

Note : Max. length of a branch line is up to 6m.

 

 

Terminating resistance

121 ohms, 1/2W ( TURCK p / n = RSM57TR2 )

Cable specification

Item

Thick cable

Thin cable

Signal

Power

Signal

Power

 

Conductor

0.82mm2

1.65mm2

0.20mm2

0.33mm2

section area

 

 

 

 

Color

Blue ( CAN-L )

Red ( 24VDC ),

Blue, White

Red, Black

White ( CAN-H )

Black ( 0VDC )

 

 

 

Impedance

120 ohms±10%

-

120 ohms±10%

-

Propagation

 

 

 

 

delay

1.36ns / ft

-

1.36ns / ft

-

( Maximum )

 

 

 

 

Attenuation

500kHz : 0.25dB / ft

 

500kHz : 0.50dB / ft

 

rate

125kHz : 0.13dB / ft

-

125kHz : 0.29dB / ft

-

( Maximum )

1.00MHz : 0.40dB / ft

 

1.00MHz : 0.70dB / ft

 

Conductor

 

 

 

 

resistance

6.9 ohms / 1000ft

3.6 ohms / 1000ft

28 ohms / 1000ft

17.5 ohms / 1000ft

( Maximum )

 

 

 

 

 

 

 

 

1ft 0.3048m