EX500 Serial System

EX## - OME0008

5 -4 -1. Address setting switch ( SW1, 2 )

These switches set node address. The setting is shown in Table 1.

5 -4 -2. Data rate setting switch ( SW3 )

This switch set data rate. The setting is shown in Table 2.

The factory default address and data rate are 63 and 125 k bit / sec. respectively.

 

 

 

X10

 

 

 

X1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1

 

SW2

 

 

 

 

 

 

 

 

SW1

SW2

 

NODE ADDRESS

 

0

 

0

 

 

0

 

0

 

1

 

 

1

 

0

 

2

 

 

2

 

 

 

 

 

6

 

3

 

 

63

 

6

 

4

 

 

PGM

 

 

 

 

 

9

 

9

 

 

 

Table 1

5 -5. I/O memory map

SW3

SW3

DATA RATE

0125 k bit / sec.

1250 k bit / sec.

2500 k bit / sec.

PGM

9

 

When PGM mode is chosen, the address and data rate are set through network.

Table 2

The GW Unit can control 128 input / output points in total. Regardless of I/O points of the equipment, it always occupies each data memory area for 64 inputs and 64 outputs.

Once the address is assigned in the GW Unit, every port then corresponds to a specific “Word” respectively. So “Word (n)” always corresponds to COM A, “Word (n+1)” corresponds to COM B, and so on.

Ex.) n = 1

In case of the input data, the sensor signal data of the Input Manifold which was connected with the COM A port, occupies "Word1" of the I/O memory mapping.

If a sensor signal is stored in the "0 bit" of the Input Manifold, it becomes like the Figure below. In the same way, in the case of the output data, the contents displayed in "Word1" of the

I/O memory mapping is output by the COM A port.

 

Branch

 

 

 

Data ( 2 byte )

 

 

 

( m,n=0 - )

MSB

LSB

MSB

LSB

connector

 

15

 

 

8

7

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word ( n )

COM A

 

 

Byte (m+1)

 

 

 

 

 

Byte (m)

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word ( n+1 )

COM B

 

 

 

 

 

 

 

 

 

 

 

 

 

Byte (m+3)

 

 

 

 

Byte (m+2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word ( n+2 )

COM C

 

 

 

 

 

 

 

 

 

 

 

 

 

Byte (m+5)

 

 

 

 

Byte (m+4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word ( n+3 )

COM D

 

 

 

 

 

 

 

 

 

 

 

 

 

Byte (m+7)

 

 

 

 

Byte (m+6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

:

 

 

 

 

 

 

 

 

 

 

 

 

 

:

:

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

Read carefully the user manual of PLC which is used as a master.

The method of PLC setup, reading from or writing to memory differ from one PLC manufacturer to another.

- 24 -

Page 25
Image 25
SMC Networks EX500 manual Address setting switch SW1, Data rate setting switch SW3, I/O memory map