Gas Requirements
Gas Supply Pipe Looping and Sizing
1
3
2
6 | 7 | 8 | 9 |
|
|
|
10
5
11
134
12
T494I
1Gas Furnace (120,000 Btu/hr)
2Gas Water Heaters (400,000 Btu/hr each)
3Gas Space Heaters (70,000 Btu/hr each)
419 ft. (5.8 m)
525 ft. (7.6 m)
6Main Regulator
7Gas Meter
8Pressure Regulator (If required)
9Gas Tumblers (120,000 Btu/hr each)
10Gas Line Pressure Tap
111 in. (25.4 mm) Gas Pipe Loop
12NOTE: Minimum Pipe Size is 1/2 in. (12.7 mm)
13
SAMPLE CALCULATIONS:
Equivalent length = Total length of main gas supply pipe to the far end of the tumblers.
| = 25 ft. + 19 ft. (7.6 m + 5.8 m) gas supply pipe |
| = 44 ft. (13.4 m) Total Gas Line |
Total Btu/hr | = The sum of the Btu/hr of all tumblers being fed by the main gas supply pipe. |
| = 9 x 120,000 |
| = 1,080,000 Btu/hr |
Using Table 9, the main supply pipe diameter should be 2 in. (51 mm).
IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers connected to single gas service. Other gas using appliances should be connected upstream from loop.