Electrical Requirements
75 Pound Tumbler Electrical Requirements
Refer to Table 13.
NOTE: Minimum wire sizes are obtained from the Canadian Electrical Code and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
|
| Terminal Block | Rated | Breaker | Breaker | Recommended | |
Heat Source | Serial Plate Voltage | Connections | |||||
Current | Rating | Poles | Wire Size | ||||
|
| Required | |||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
Gas and Steam | 120 Volt/60 Hertz/ | L1, Neutral and ground | * | 20 Amps | 1 | 12 AWG | |
| 1 Phase |
|
|
|
| (3.9 mm2) | |
Gas and Steam | 208 or 240 Volt/ | L1, L2, Neutral and | * | 15 Amps | 2 | 14 AWG | |
| 60 Hertz/1 Phase | ground |
|
|
| (2.6 mm2) | |
Gas and Steam | L1, Neutral and ground† | * | 15 Amps | 1 | 14 AWG | ||
| 1 Phase |
|
|
|
| (2.6 mm2) | |
Gas and Steam | 208 or 240 Volt/ | L1, L2, L3, and ground† | * | 15 Amps | 3 | 14 AWG | |
| 60 Hertz/3 Phase |
|
|
|
| (2.6 mm2) | |
Gas and Steam | 380 or 415 Volt/ | L1, L2, L3 and ground | * | 15 Amps | 3 | 14 AWG | |
| 50 Hertz/3 Phase |
|
|
|
| (2.6 mm2) | |
Gas and Steam | L1, L2, L3 and ground | * | 15 Amps | 3 | 14 AWG | ||
| 3 Phase |
|
|
|
| (2.6 mm2) | |
Electric | 208 Volt/60 Hertz/ | L1, L2, L3 and ground | 88 Amps | 100 Amps | 3 | 2 AWG | |
| 3 Phase |
|
|
|
| (43 mm2) | |
Electric | 240 Volt/60 Hertz/ | L1, L2, L3 and ground | 78 Amps | 90 Amps | 3 | 2 AWG | |
| 3 Phase |
|
|
|
| (43 mm2) | |
Electric | 240 Volt/50 Hertz/ | L1, L2, L3 and ground | 78 Amps | 90 Amps | 3 | 2 AWG | |
| 3 Phase |
|
|
|
| (27 mm2) | |
Electric | 380 Volt/50 Hertz/ | L1, L2, L3 and ground† | 50 Amps | 60 Amps | 3 | 4 AWG | |
| 3 Phase |
|
|
|
| (27 mm2) | |
Electric | 415 Volt/60 Hertz/ | L1, L2, L3, and ground† | 46 Amps | 60 Amps | 3 | 4 AWG | |
| 3 Phase |
|
|
|
| (27 mm2) | |
Electric | 480 Volt/60 Hertz/ | L1, L2, L3, and ground | 38 Amps | 50 Amps | 3 | 6 AWG | |
| 3 Phase |
|
|
|
| (17 mm2) |
*Current Ratings vary slightly depending on model; refer to serial plate.
†MT (manual timer)/CD (rotary coin drop) Models may require a Neutral conductor. Consult wiring diagram.