The steam trap must be installed and the coil outlet connections must be connected to the condensate return lines. The following steps outline the procedure for installing the steam trap and connecting the condensate return lines. Refer to Figure 15 for typical installations.
1.Connect a flexible hose to each steam coil outlet.
2.Install a strainer to the ends of each flexible hose.
3.Install a steam trap to each strainer.
IMPORTANT: Steam trap must be installed a minimum of 18 inches (457 mm) below the steam coil outlet connections.
4.Install a globe
5.Connect to the condensate return lines.
Steam Requirements
WARNING
The flexible steam hoses connecting the coil outlet connections and steam traps must have a minimum of 125 psig (pounds per square inch gauge) (8.79 kg/ sq. cm.) working pressure. A
Each steam trap must be supported so minimum load is exerted on the coil outlet connection.