-Enter original password.
Alarm Setup
There are several alarms in the blender control they are as follows:
No Flow - | No weight loss is being detected on the feeder in question. This would |
| indicate a faulty load cell, a material bridge in the |
| something obstructing load cell movement. |
Weigh hopper is not being | |
| caused by the supply hoppers not be kept full. Check the loading system. |
No material - | This means the weigh hopper is empty. |
Load cell Failure - The controller is not properly reading the load cell. Check the load cell.
Load cell over ma x- The maximum weight limit on the load cell is exceeded. Check weigh hopper size and material bulk density.
Extruder No Flow - No
Blender Cannot keep up - The extruder is running faster than the augers will allow the blender to run.
There are several options to set for the above listed alarms. The following explains the options and how to set them up.
Continuous | Chapter 3: Installation | 40 |