INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
TIMBER FRAMED BUILDINGS
1.5It will be necessary to provide additional clearance when the flue passes through a wall containing any combustible materials so as to prevent a fire hazard.
1.6The hole through which the flue will pass, must have a steel sleeve which is positioned so that an air gap of at least 25mm is maintained between the outer surface of the flue, and any part of the sleeve.
1.7For further guidance on the installation of gas appliances in timber framed buildings, contact your local buildings control authority.
2.GAS SUPPLY
2.1Before installation, ensure that the local distribution conditions (identification of the gas type and pressure) and the adjustment of the appliance are compatible.
2.2Ensure that the gas supply is capable of delivering the required amount of gas, and is in accordance with the rules in force.
2.3
2.4This appliance is supplied complete with a factory fitted isolation device incorporated into the inlet connection. No further isolation device is therefore required.
3.ventilation
3.1This appliance requires no additional ventilation.
4.Appliance location
NOTE: It is recommended you construct the back panel of the fireplace from natural materials cut into three or more sections to prevent cracking.
4.1This appliance must stand on a non combustible hearth that is at least 12mm thick. If the fire is greater than 50mm above the floor, then no hearth is required, although due consideration should be given to how the heat may affect the floor material.
4 | A |
|
|
|
|
|
| B | D |
|
|
|
|
|
| DIMENSIONS | MIN | MAX |
| |
|
|
|
| |||
|
|
| A | 420 mm | 450 mm |
|
| C |
|
|
|
|
|
|
| B | 560 mm | 575 mm |
| |
|
|
|
| |||
|
|
| C | 237 mm | - |
|
| E |
| D | 300 mm | - |
|
|
| E | 420 mm | - |
| |
|
|
|
| |||
|
|
| F | 12 mm | - |
|
| F |
|
|
| AR0184 | |
|
|
|
|
| ||
|
|
|
|
|
|
|
4.2The minimum opening dimensions are shown, Diagram 4.
4.3This appliance can only be installed on an outside wall with suitable clearances for the flue terminal and guard (if required).
4.4This appliance is not suitable for installation into a combustible wall. All combustible material must be removed from the area shown, Diagram 5.
5720
300 |
|
|
560 |
| 860 |
150 | 420 | AR1227 |
|
4.5The maximum depth of combustible shelf is 150mm at a minimum height of 300mm above the fireplace opening.