INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
1. Flue and Chimney Requirements
NOTE: This appliance can only be installed in conjunction with the flue supplied.
1.1The flue must be sited in accordance with BS5440: Part 1 (latest edition), Diagram 1.
1.2Any terminal which is less than 2 metres above any access (level ground, balcony or above a flat roof to which people have access) is to be fitted with a guard.
1.3The flue must be securely fixed and fire precautions followed in accordance with local and national codes of practice.
1.4The horizontal terminal can be reduced in length, Diagram 2.
2
AR0630
1
UK Dimensions
Dimension | Terminal Position | Minimum |
|
| Distance |
|
| (mm) |
A* | Directly below an opening, air brick, opening widows etc | 300 mm |
|
|
|
B* | Above an opening, air brick, opening windows etc. | 300 mm |
|
|
|
C* | Horizontal to an opening, air brick, opening windows etc. | 300 mm |
|
|
|
D | Below gutters, soil pipes or drain pipes | 300 mm |
|
|
|
E | Below eaves | 300 mm |
|
|
|
F | Below balconies or car port roof | 600 mm |
|
|
|
G | From a vertical drain pipe or soil pipe | 300 mm |
|
|
|
H | From an internal or external corner | 600 mm |
|
|
|
I | Above ground, roof or balcony level | 300 mm |
|
|
|
J | From a surface facing the terminal (or boundary) | 600 mm |
|
|
|
K | From a terminal facing the terminal | 600 mm |
|
|
|
L | From an opening in the car port (e.g. door, window) into dwelling | 1200 mm |
|
|
|
M | Vertically from a terminal on the same wall | 1500 mm |
|
|
|
N | Horizontally from a terminal on the same wall | 300 mm |
|
|
|
O | From the wall in which the terminal is mounted | N/A |
|
|
|
P | From a vertical structure on the roof | N/A |
|
|
|
Q | Above intersection with roof | N/A |
|
|
|
*In addition, the terminal should not be nearer than 300mm to an opening in the building fabric formed for the purpose of accommodating a
HThe reference to external corners does not apply to building protrusions not exceeding 450mm, such as disused chimneys on external walls.