SITE REQUIREMENTS

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1. Flue and Chimney Requirements

NOTE: This appliance can only be installed in conjunction with the flue supplied.

1.1The flue must be sited in accordance with BS5440: Part 1 (latest edition), Diagram 1.

1.2Any terminal which is less than 2 metres above any access (level ground, balcony or above a flat roof to which people have access) is to be fitted with a guard.

1.3The flue must be securely fixed and fire precautions followed in accordance with local and national codes of practice.

1.4The horizontal terminal can be reduced in length, Diagram 2.

2

AR0630

1

UK Dimensions

Dimension

Terminal Position

Minimum

 

 

Distance

 

 

(mm)

A*

Directly below an opening, air brick, opening widows etc

300 mm

 

 

 

B*

Above an opening, air brick, opening windows etc.

300 mm

 

 

 

C*

Horizontal to an opening, air brick, opening windows etc.

300 mm

 

 

 

D

Below gutters, soil pipes or drain pipes

300 mm

 

 

 

E

Below eaves

300 mm

 

 

 

F

Below balconies or car port roof

600 mm

 

 

 

G

From a vertical drain pipe or soil pipe

300 mm

 

 

 

H

From an internal or external corner

600 mm

 

 

 

I

Above ground, roof or balcony level

300 mm

 

 

 

J

From a surface facing the terminal (or boundary)

600 mm

 

 

 

K

From a terminal facing the terminal

600 mm

 

 

 

L

From an opening in the car port (e.g. door, window) into dwelling

1200 mm

 

 

 

M

Vertically from a terminal on the same wall

1500 mm

 

 

 

N

Horizontally from a terminal on the same wall

300 mm

 

 

 

O

From the wall in which the terminal is mounted

N/A

 

 

 

P

From a vertical structure on the roof

N/A

 

 

 

Q

Above intersection with roof

N/A

 

 

 

*In addition, the terminal should not be nearer than 300mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame.

HThe reference to external corners does not apply to building protrusions not exceeding 450mm, such as disused chimneys on external walls.

14

Page 14
Image 14