Superior DR-400CMN Pilot for SIT Millivolt Gas Valve Pilot Orifice, Honeywell Millivolt Gas Valve

Models: DR-400CMN DR-400CEP DT-400CMN DT-400CMP DR-400CEN DT-400CEN DT-400CEP DR-400CMP

1 28
Download 28 pages 33.19 Kb
Page 27
Image 27
Pilot for SIT Millivolt Gas Valve

Pilot for SIT Millivolt Gas Valve

Pilot

Orifice

Figure 60

b. Attach manometer to the manifold side pressure test fitting and verify manifold pres- sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.

c. Refer to Figure 60 and remove the pilot hood assembly to access the hexed pilot ori- fice. Remove and replace the orifice with the one provided with the kit.

Pilot for Honeywell Millivolt Gas Valve

(Loosening of Hex Fitting For Orifice Strip Tab Positioning)

Hood

Hood Alignment

7/16 in. Open End Wrench

 

Orifice Strip Tab

 

Take Care Not to Contact the Orifice Strip Tab

Figure 62

with the Hex Fitting Wrench - Distortion of the Tab

May Render the Pilot Inoperative.

 

 

 

 

 

Pilot for Honeywell Millivolt Gas Valve

 

Orifice Strip Tab Position Identification

 

For LP/Propane and Natural Gas

Step 5. Millivolt Appliances -

Honeywell Systems

a. Convert the gas valve as follows (see Figure 61): Remove the plastic protecting cap. Remove the gas type setting screw by turning it counter- clockwise. Obtain the replacement gas type

LP/Propane Gas Position -

1/16 in. Hole, LP and

Red Color shown on tab

L

P

Natural Gas Position -

NAT shown on tab

NAT

setting screw from the kit and screw it into place (red for propane and blue for natural gas). Tighten the gas type setting screw by turning it clockwise. Replace the plastic protecting cap.

Honeywell Millivolt Gas Valve

Adjusting Knob

Regulator Cap

Conversion screw

(blue natural gas;

red LP/propane gas)

Figure 61

Figure 63

Top View of Hex Fitting and Orifice Strip Tab

 

 

 

 

 

Pilot for Honeywell Millivolt Gas Valve Orifice Strip Tab Positioning

 

Pilot Hood Position After

 

Loosening Hex Fitting 1/4 Turn

 

Orifice Strip Tab

 

Push Tab to Set

 

Gas Type Usage

 

Note - Orifice Strip Tab May

 

Be Randomly Located On Any

Figure 64

Side Of The Hex Fitting

 

 

 

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

27