Superior DT-400CEP, DR-400CMP Horizontal Outside Wall Termination System, A. Plan the vent run

Models: DR-400CMN DR-400CEP DT-400CMN DT-400CMP DR-400CEN DT-400CEN DT-400CEP DR-400CMP

1 28
Download 28 pages 33.19 Kb
Page 14
Image 14
HORIZONTAL (OUTSIDE WALL)

HORIZONTAL (OUTSIDE WALL)

TERMINATION SYSTEM

Figures 28, and Figures 34 to 41 on pages 16 to

18and their associated Horizontal Vent Table illustrate the various horizontal venting configura- tions that are possible for use with these appli- ances. Secure Vent pipe applications are shown in these figures; Secure Flex pipe may also be used. AHorizontalVentTablesummarizeseachsystem’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications. Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to Figure 8 on page 6 for location guidelines.

Secure Vent SV4.5 direct vent system compo-

 

TYPICAL HORIZONTAL VENT INSTALLATION

 

Building

Support

Horizontal / Inclined Run

SV4.5HTSSL

Support

Brackets

 

 

Termination

Framing

 

 

 

 

 

 

Shown

 

 

 

 

SV4.5E90

 

 

 

 

Elbow

 

 

 

 

 

 

 

Firestop/Spacer

Exterior

Ceiling

 

SV4.5L6/12/24/36/48

Wall

 

 

*Ceiling

Vent Sections

SV4.5HTSSL

 

 

Vertical

 

Firestop/Spacer

 

 

Support Bracket Spacing

Termination

Rise

 

(SV4.5BF)

 

Every 5 ft (1.52 m)

Shown

 

 

 

 

 

*When using Secure Flex

 

 

 

use Firestop/Spacer

 

 

 

(SF4.5BF)

 

 

 

See Figure 17 on page 10

 

 

Fireplace

for vertical vent section

Exterior

 

support.

Fireplace

Figure 28

 

 

 

Wall

 

 

 

 

14

nents are unitized concentric pipe components featuring positive twist lock connection, (refer to Figure 15 on page 10). All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the types and quantities of sections required 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm) net section lengths are available. Make allow- ances for elbows as indicated in Figure 18 on page 10. Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.

B. Frame exterior wall opening -

Locatethecenteroftheventoutletontheexteriorwall according to the dimensions shown in Figure 9 on page 7. Cut and/or frame an opening, 10¹⁄₂" x 12¹⁄₈" (267 mm x 308mm) inside dimensions, about this center.

C. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/or frame an opening, 10¹⁄₂" x 10¹⁄₂" (267

mmx 267 mm) inside dimensions, about this center (refer to Figure 14 on page 10 ).

D. Attach vent components to appliance - To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (refer to Figure 15 on page 10). Push the vent component against the collar until it fully engages, then twist the com- ponent clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure.

Sealant and securing screws are not required.

Note: An elbow may also be attached to the appliance collar. Attach in the same manner as you would a vent section.

E.Attach vent components to each other - Other vent sections may be added to the previ- ously installed section in accordance with the requirements of the vent tables. To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 16 on page 10.

F.Install firestop/spacer at ceiling -

When using Secure Vent, use SV4.5BF fir- estop/spacer at ceiling joists; when using Se- cure Flex, use SF4.5BF firestop/spacer. If there is living space above the ceiling level, the fir- estop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and se- cure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.

Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.

G. Support the vertical run sections -

On the vertical run, support the venting system every 8 feet (2.4m) above the fireplace vent outlet with field provided support straps (Plumber's tape). Attach the straps to the vent pipe and secure to the framing members with nails or screws. See Figure 17 on page 10.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

H. Change vent direction - At transition from or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sec- tions. See Figure 18 on page 11.

I. Continue installation of horizontal/inclined sections - Continue with the installation of the straight vent sections in horizontal/inclined run as described in Step E. Install support straps every 5 ft. (1.52 m) along horizontal/ inclined vent runs using conventional plumber’s tape. See Figure 28. It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of ¹⁄₄" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.

It is important to maintain the required clear- ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.

J. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B

When using square (SV4.5 HTS), short square (SV4.5 HTSS) or round (SV4.5HTR) horizon- tal termination -

Assemble the vent system to point where the terminus of the last section is within 6 in. (152

mm)to 10¹⁄₄ in. (260 mm) inboard of the exterior surface to which the termination is to be attached, see Figure 31 on page 15.

Page 14
Image 14
Superior DT-400CEP Horizontal Outside Wall Termination System, A. Plan the vent run, B. Frame exterior wall opening