Thermo Products CMA1-50N, CMA2-75N service manual V.Starting The Unit A. Sequence Of Operations

Models: CMA1-50N CMA2-75N

1 55
Download 55 pages 9.18 Kb
Page 35
Image 35
V.STARTING THE UNIT

All installations and services must be performed by qualified service personnel.

V.STARTING THE UNIT

A. SEQUENCE OF OPERATIONS

AT ANY TIME THE

 

 

 

CONTINUOUS SAFE OPERATION CHECK

GAS VALVE IS

 

 

 

IF FLAME SIMULATION CONDITION

NOT ENERGIZED

 

 

PRESENT OR ROLL-OUT SWITCH OPENS, SYSTEM

 

 

 

ENERGIZES INDUCER FAN FOR 15 SECONDS AND CIRCULATOR BLOWER AT

START

 

 

HEATING SPEED UNTIL SITUATION CORRECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT CALLS FOR

 

 

 

 

 

 

 

HEAT, CONTACTS CLOSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL BOARD ENERGIZED,

 

 

 

 

 

INDUCER ENERGIZED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE SWITCH SENSES

 

 

ADEQUATE DIFFERENTIAL PRESSURE,

 

 

 

 

 

CONTACTS CLOSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER IS APPLIED TO

 

POWER INTERRUPTION

THE SILICON NITRIDE

 

SYSTEM SHUTS OFF,

IGNITOR. IGNITOR

 

RESTARTS WHEN POWER

WARM-UP IS 20 SECONDS.

 

IS RESTORED.

START

 

 

 

AFTER IGNITOR WARM-UP,

 

TRIAL

 

THE GAS VALVE IS

 

FOR

 

ENERGIZED TO OPEN

 

IGNITION

 

 

 

 

 

 

 

 

 

FLAME MUST BE DETECTED

 

IF FLAME IS NOT DETECTED, THE

WITHIN 4 SECONDS IF

 

GAS VALVE IS DE-ENERGIZED,

FLAME IS DETECTED, THE

 

THE IGNITOR IS TURNED OFF AND

 

DELAY-TO-FAN-ON TIME

 

THE CONTROL BOARD CONTROL GOES

BEGINS (45 SECONDS)

 

INTO "RETRY" SEQUENCE.

33

Page 35
Image 35
Thermo Products CMA1-50N, CMA2-75N service manual V.Starting The Unit A. Sequence Of Operations