Thermo Products CMA1-50N Gas Pressure Chart For Cma* Model Furnaces, D.Burner Adjustment

Models: CMA1-50N CMA2-75N

1 55
Download 55 pages 9.18 Kb
Page 39
Image 39
GAS PRESSURE CHART FOR CMA* MODEL FURNACES

All installations and services must be performed by qualified service personnel.

GAS PRESSURE CHART FOR CMA* MODEL FURNACES

 

SUPPLY PRESSURE

MANIFOLD PRESSURE

 

 

 

NAT

MAX 14” WC

3.5 + .3” WC

MIN 4.5” WC

 

 

PROPANE

MAX 14” WC

10.0” + .3” WC

MIN 11” WC

 

 

 

 

 

 

TABLE 3

 

This gas furnace is equipped with a fixed orifice sized for the manifold pressure shown on the rating label. The input can only be increased, or decreased, by adjusting the manifold pressure. Remove the 1/8" threaded pipe plug located on the gas manifold.

Use a U tube manometer or recently calibrated pressure gage to measure the pressure. To adjust the pressure, remove the screw cap from the regulator on the gas valve and using the adjustment screw. Decrease the pressure by turning the screw counterclockwise or increase it by turning the screw clockwise.

D.BURNER ADJUSTMENTManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background : ADJUSTMENTS TO THE LISTED PRESSURE MUST NOT EXCEED 0.3" WC. A 0.3" WC adjustment will increase or decrease the input approximately 4.0%.

Replace screw (cap) when adjustment is complete.

The correct input can be assumed if the furnace manifold pressure is the same as that shown on the rating label if a gas meter is not available for natural gas or the unit is installed on an unmetered propane gas supply.

Shut off the gas supply to the furnace. Remove the pressure gage and re- install the pipe plug using a thread compound resistant to the action of LP gases.

If the rated input cannot be obtained with the present orifice at the correct pressure, your local gas supplier may assist in sizing the proper orifice. Thermo Products Engineering Department will gladly assist in sizing the orifice if you provide them with the heating value in BTU per cubic foot and the specific gravity of the fuel gas.

D.BURNER ADJUSTMENT

This unit is designed to not require any burner adjustment. The flames should be checked by looking through the sight glass located on the burner box. Burner