AT THE INTEGRATED CONTROL?

All installations and services must be performed by qualified service personnel.

Yes

Yes

 

IS THERE LINE VOLTAGE ACROSS INDUCER POWER TERMINALS "IND" & "IND N"

AT THE INTEGRATED CONTROL?

Yes

CHECK WIRING TO INDUCER

AND IF OK, REPLACE

INDUCER ASSEMBLY.

No

CHECK THE INTEGRATED

CONTROL DIAGNOSTIC LED

LAMP. RESET BY INTERRUPTING POWER TO CONTROL FOR MORE THAN ONE SECOND. IF LED STAYS ON CONTINUOUSLY, REPLACE INTEGRATED CONTROL.

DOES THE HOT

No

IS THERE VOLTAGE PRESENT

No

CHECK THE INTEGRATED CONTROL

SURFACE

DIAGNOSTIC LED LAMP. RESET BY

 

AT THE HOT SURFACE

 

IGNITOR ENERGIZE

 

INTERRUPTING POWER TO CONTROL

 

IGNITOR TERMINALS

AND GLOW?

 

 

FOR MORE THAN ONE SECOND. IF

 

"IGN" & "IGN N" AT THE

 

 

 

 

LED STAYS ON CONTINUOUSLY,

 

 

INTEGRATED CONTROL?

 

 

 

 

REPLACE INTEGRATED CONTROL.

 

 

 

 

 

 

Yes

 

 

 

 

 

CHECK WIRING TO

 

 

 

Yes

 

HOT SURFACE IGNITOR

 

 

 

 

AND IF OK, REPLACE

 

 

 

 

 

 

 

 

 

HOT SURFACE IGNITOR ASSEMBLY.

 

 

 

 

CHECK ACROSS "MV"

 

 

AFTER HOT SURFACE

 

TERMINALS ON INTEGRATED

No

 

No

CONTROL FOR 24 VOLTS DURING

SAME AS ABOVE.

IGNITOR WARM-UP,

 

THE 4 SECOND FLAME PROVING

 

 

 

 

DOES GAS VALVE OPEN?

 

PERIOD AFTER IGNITOR WARM-UP.

 

 

 

IS THERE 24VOLTS?

 

 

Yes

 

Yes

 

 

 

 

 

 

 

 

 

 

CHECK WIRING TO GAS

 

 

 

 

 

VALVE AND IF OK,

 

 

 

 

 

REPLACE GAS VALVE.

 

 

 

46

Page 48
Image 48
Thermo Products CMA2-75N, CMA1-50N service manual At The Integrated Control?