Tightening connection

Under Ceiling Type

Installation Manual

Tightening connection

▼Tightening torque of flare pipe connections CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit: ft•lbs (N•m))

Outer dia. of copper

Tightening torque

pipe

 

1/4” (6.4 mm)

10 -13 (14 - 18)

 

 

3/8” (9.5 mm)

24 - 31 (33 - 42)

 

 

1/2” (12.7 mm)

37 - 46 (50 - 62)

 

 

5/8” (15.9 mm)

46 - 57 (63 - 77)

 

 

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.

„Evacuation

Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.

For details, follow to the Installation Manual attached to the outdoor unit.

Never use the refrigerant sealed in the outdoor unit for air purge.

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor

(Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Flare at indoor „Evacuation unit side

Refrigerant amount to be added Flare at Piping with outdoor unitOpen the valve fully outdoor unit side

unit.

Be sure to use a scale to charge the refrigerant of specified amount.

REQUIREMENT

Charging an excessive or too little amount of

 

refrigerant causes a trouble of the compressor.

 

Be sure to charge the refrigerant of specified

 

amount.

A personnel who charged the refrigerant should

 

write down the pipe length and the added

Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union Gas leak check– 12 –Manual backgroundManual backgroundFlare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

Piping with outdoor unit

Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit.

refrigerant amount in the nameplate attached to the

service panel of the outdoor unit. It is necessary to

troubleshooter the compressor and refrigeration

cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully.

For details, refer to the Installation Manual attached to the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).

EN

– 12 –

12-EN

Page 13
Image 13
Toshiba RAV-SP240CT-UL „Evacuation, Tightening connection, Refrigerant amount to be added, Piping with outdoor unit