Toshiba RAV-SP180CT-UL „Remote control switch monitoring function, Under Ceiling Type

Models: RAV-SP360CT-UL RAV-SP240CT-UL RAV-SP180CT-UL RAV-SP300CT-UL RAV-SP420CT-UL

1 34
Download 34 pages 45.46 Kb
Page 27
Image 27
„Remote control switch monitoring function

Under Ceiling Type

„Remote control switch monitoring function

This function is available to call the service monitor mode from the remote control during a test run to acquire temperatures of sensors of the remote control, indoor unit, and outdoor unit.

1.Push – 26 – and Manual backgroundManual background buttons simultaneously for at least 4 seconds to call the service monitor mode.

The service monitor indicator lights up and the header indoor unit number is displayed first. CODE

No. Manual backgroundManual backgroundManual backgroundManual background is also displayed.

2.Pushing TEMP. Manual backgroundManual background buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)

3.Pushing Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background (left side of the button), select an indoor unit to be monitored. The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.

4.Push Manual background button to return to the normal display.

Installation Manual

 

Outdoor unit data

 

 

CODE No.

Data name

 

 

60

Outdoor unit heat exchanger temperature

(TE)

 

61

Outside air temperature (TO)

 

 

62

Compressor discharge air temperature (TD)

 

 

63

Compressor intake air temperature (TS)

 

 

64

 

 

65

Heatsink temperature (THS)

 

 

6A

Operating current (x1/10)

 

 

F1

Compressor cumulative operating hours

(x100h)

 

2

4

1 3

 

Indoor unit data

 

 

CODE No.

Data name

 

 

01

Room temperature (remote control)

 

 

02

Indoor unit intake air temperature (TA)

 

 

03

Indoor unit heat exchanger temperature

(TCJ)

 

04

Indoor unit heat exchanger temperature

(TC)

 

F3

Indoor unit fan cumulative operating hours

(x1 h)

 

F8

Indoor unit discharge air temperature

 

 

EN

– 26 –

26-EN

Page 27