Procedure 1
Turn on the circuit breaker of the air conditioner. The operation is not accepted for 5 minutes when circuit breaker is turned on at first time after installation, and 1 minute when circuit breaker is turned on at the next time and after. After the specified time has passed, perform a test operation.
Procedure 2
Push “ON/OFF” button on the remote control, select [COOL] or [HEAT] with “MODE” button, and then select [HIGH] with “FAN” button.
Procedure 3
Cooling test run | Heating test run |
|
|
Set the temperature to 64°F | Set the temperature to 86 °F |
(18°C) with the temp. setup | (30°C) with the temp. setup |
buttons. | buttons. |
Procedure 4
Cooling test run | Heating test run |
|
|
After confirming a signal | After confirming a signal |
receiving sound “beep” | receiving sound “beep” |
immediately set the | immediately set the |
temperature to 66 °F (19°C) | temperature to 84 °F (29°C) |
with the temp. setup buttons. | with the temp. setup buttons. |
Procedure 5
Cooling test run | Heating test run |
|
|
After confirming a signal | After confirming a signal |
receiving sound “beep” | receiving sound “beep” |
immediately set the | immediately set the |
temperature to 64 °F (18°C) | temperature to 86 °F (30°C) |
with the temp. setup buttons. | with the temp. setup buttons. |
Procedure 6
Repeat procedures 4 → 5 → 4 → 5.
Indicators “Operation” (green), “Timer” (green), and “Ready” (orange) in the wireless receiver section flash in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash, repeat procedures
2 to 5.
Procedure 7
Upon completion of the test run, push “ON/OFF” button to stop operation.
<Overview of test run operations using the wireless remote control>
▼Cooling test run:
ON/OFF → 64 °F (18 °C) → 66 °F (19°C) → 64 °F (18°C) → 66 °F (19°C) → 64 °F (18°C) → 66 °F (19°C)
→64 °F (18°C) → (test run) → ON/OFF
▼Heating test run:
ON/OFF → 86 °F (30°C) → 84 °F (29°C) → 86 °F (30°C) → 84 °F (29°C) → 86 °F (30°C) → 84 °F (29°C)
→86 °F (30°C) → (test run) → ON/OFF
Always select |
| |
[HIGH] fan |
| |
speed. | 3, 4, | |
2 | ||
2 | 5, 6 | |
2,7 | ||
|
EN |