8 TEST RUN

Under Ceiling Type

Installation Manual

8 TEST RUN

„Before test run

Before turning on the circuit breaker, carry out the following procedure.

1)Using 500V-megger, check 1MΩ or more exists between the terminal block L1 to L2 and the ground.

If 1MΩ or less is detected, do not run the unit. Do not apply to the remote control circuit.

2)Check the valve of the outdoor unit being opened fully.

To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.

„Execute a test run

Using the remote control, operate the unit as usual. For the procedure of the operation, refer to the attached Owner’s Manual.

A forced test run can be executed in the following procedure even if the operation stops by thermo.-OFF. In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation.

„Before test run CAUTION

Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.

Wired remote control

„Execute a test runWired remote control 2, 4  2, 4  3– 27 –Manual background 3

1,5

Procedure 1

Keep Manual backgroundManual background button pushed for 4 seconds or more. [TEST] is displayed on the display part and the selection of mode in the test mode is permitted.

Procedure 2

Push Manual background button.

Procedure 3

Using Manual background button, select the operation mode, [COOL] or [HEAT].

Do not run the air conditioner in a mode other than [COOL] or [HEAT].

The temperature controlling function does not work during test run.

The detection of error is performed as usual.

Procedure 4

After the test run, push Manual backgroundManual backgroundManual backgroundManual backgroundManual background button to stop a test run.

(Display part is same as procedure 1.)

Procedure 5

Push Manual background check button to cancel (release from) the test run mode.

([TEST] disappears on the display and the status returns to a normal.)

27-EN

– 27 –