Electrical Installation Procedure

Dimensions &

Weights VFD

Electrical Installation Procedure

Refer to the National Electric Code, section 310-16 for sizing wires 4B - 9B. All other control wires should be twisted shielded or twisted pair shielded, 20 - 14 AWG, with lead length not to exceed 164 feet. When using shielded wire, the shield sheath must be connected at the VFD only.The connection on units withVFD is J13-S.The connection on unis withVFD/ bypass is ITBI-10.

Variable Frequency Drive with Bypass

C

A

B

FD

E

VFD with bypass dimensions, in.

G

H

voltage

hp

A

B

C

D

E

F

G

H

460

7.5

30.40

28.03

16.14

23.35

24.85

0.75

8.59

10.63

 

10

 

 

 

 

 

 

 

 

208

7.5

41.28

38.89

16.14

24.00

25.5

0.75

10.95

12.99

 

10

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

46015

20

25

208

25

50.81

48.35

21.36

31.61

33.41

0.90

12.36

14.41