Trane SCXG-SVX01B-EN manual general Operation information, Emergency Stop Input, VAV Box Option

Models: SCXG-SVX01B-EN

1 116
Download 116 pages 5.51 Kb
Page 72
Image 72
Emergency Stop Input

general

Operation information

must be rated for 12 ma @ 24VDC minimum. This input will override all VOM inputs, if the VOM option is on the unit.

Occupied/Unoccupied Contacts To provide night setback control if a remote panel with night setback was not ordered, install a field-supplied contact. This binary input provides the building’s occupied/unoccupied status to the RTM. It can be initiated by a time clock, or a building automation system control output.The relay’s contacts must be rated for 12 ma @ 24 VDC minimum. Refer to the appropriate wiring diagrams (attached to the unit control panel for the proper connection terminals in the unit control panel.

Emergency Stop Input

A binary input is provided on the RTM board for installation of a field-supplied normally closed (N.C.) switch to use during emergency situations to shut down all unit operations. When open, an immediate shutdown occurs. An emergency stop diagnostic enters the human interface and the unit will require a manual reset. Refer to the unit wiring diagrams (attached to the unit control panel for the proper connection terminals. The switch must be rated for 12 ma @ 24 VDC minimum. This input will override all VOM inputs, if the VOM option is on the unit.

VAV Box Option

To interlockVAV box operation with evaporator fan and heat/cool modes, wire the VAV boxes/air valves toVAV box control connections on the terminal block.

Supply Duct Static Pressure Control The RTM relies on input from the duct pressure transducer when a unit is equipped with IGV or VFD to position the IGV or set the supply fan speed to maintain the supply duct static pressure to within the static pressure setpoint deadband.

RTM Sensors

RTM sensors include: zone sensors with or without setpoint inputs and modes, supply air sensor, duct static pressure, outside air temperature, outside air humidity, airflow proving, and dirty filter.

Table O-GI-2. RTM sensor resistance vs. temperature

temperature, °F

resistance, Ω ohms

temperature, °F

resistance, Ω ohms

-40

346.1

71

11.60

-30

241.7

72

11.31

-20

170.1

73

11.03

-10

121.4

74

10.76

-5

103.0

75

10.50

0

87.56

76

10.25

5

74.65

77

10.00

10

63.8

78

9.76

15

54.66

79

6.53

20

46.94

80

9.30

25

40.40

85

8.25

30

34.85

90

7.33

35

30.18

100

5.82

40

26.22

105

5.21

45

22.85

110

4.66

50

19.96

120

3.76

55

17.47

130

3.05

60

15.33

140

2.50

65

13.49

150

2.05

66

13.15

160

1.69

67

12.82

170

1.40

68

12.50

180

1.17

69

12.19

190

0.985

70

11.89

200

0.830

Table O-GI-3. RTM setpoint analog inputs

cooling or heating setpoint input, °F

cooling setpoint input, °F

resistance, Ω

(using RTM as zone temp. source)

(using RTM as supply air temp. source)

ohms

 

 

40

40

1084

45

45

992

50

50

899

55

55

796

60

60

695

65

65

597

70

70

500

75

75

403

80

80

305

NA

85

208

NA

90

111

Table O-GI-4. RTM resistance value vs. system operating mode

resistance

CV units

 

VAV units

applied to RTM mode

 

input terminals, ohms

fan mode

system mode

system mode

2320

auto

off

off

4870

auto

cool

 

7680

auto

auto

auto

10,770

on

off

 

13,320

on

cool

 

16,130

on

auto

 

19,480

auto

heat

 

27,930

on

heat

 

Note: Mode boundaries are 1000 to 40,000 ohms. Other boundaries are equal to the midpoint between the nominal mode resistance.

72

SCXG-SVX01B-EN

Page 72
Image 72
Trane SCXG-SVX01B-EN manual general Operation information, Emergency Stop Input, VAV Box Option, RTM Sensors