Trane SCXG-SVX01B-EN manual general Operation information, Points List - RTM Module, Binary inputs

Models: SCXG-SVX01B-EN

1 116
Download 116 pages 5.51 Kb
Page 70
Image 70
general

general

Operation information

Points List - RTM Module

Binary inputs

Emergency stop

External auto/stop

Unoccupied/occupied

Dirty filter

VAV changeover with hydronic heat

Binary outputs

VAV box drive max (VAV units only)

CV unoccupied mode indicator (CV units only)

Alarm

Fan run request

Water pump request (water-cooled only)

Analog input

Airside economizer damper minimum position

Analog output

• Outside air damper actuator

Heat Module:

• Analog output

Points List - GBAS Module

Binary inputs

• Demand limit contacts

Binary outputs

Dirty filter relay

Refrigeration fail relay

Heat fail relay

Supply fan fail relay

Active diagnostics

Analog inputs

Occupied zone cooling setpoint

Occupied zone heating setpoint

Unoccupied zone cooling setpoint

Unoccupied zone heating setpoint or minimum outside air flow setpoint

Supply air cooling setpoint

Supply air heating setpoint

Supply air static pressure setpoint

Points List - ECEM Module

Analog inputs

Return air temperature

Return air humidity

In addition, units with aVOM have:

Binary inputs

VOM mode A, unit off

VOM mode B, pressurize

VOM mode C, exhaust

VOM mode D, purge

VOM mode E, purge w/duct pressure control

Binary outputs

• V.O. relay

Points List -TracerTMLCI-I Module

ConstantVolume (CV) Points

Binary inputs

Airside economizer enable/disable

Condensor type (air or water cooled)

Condensor water flow status

Emergency shutdown

Local fan switch enable/disable

Mechanical cooling lockout

Mechanical heating lockout

Mixed air temperature

Occupancy

Occupancy override

Occupancy sensor

Binary outputs

Airside economizer status

Alarm status

Compressor on/off status

Condensor circuit information

Condensor water pump status

Waterside economizer status

Analog inputs

Airside economizer dry bulb setpoint

Airside economizer minimum setpoint

Building static pressure input

Maintenance required time

Occupancy bypass time

Outdoor air damper minimum position setpoint

Outdoor air relative humidity

Outdoor air temperature

Unit start delay time setpoint

Zone temperature

Zone temperature setpoint

Zone temperature setpoint (default)

Zone temperature setpoint limits

Zone temperature setpoint offsets

Zone temperature setpoint shift

Analog outputs

Alarm message

Building static pressure status •Condensor saturated refrigerant temp

Condensor water temperature

Cooling output status

Effective occupancy

Exhaust fan status

Heating output status

Heating/cooling mode

Morning warm up sensor temperature

Outdoor air damper position

Outdoor air enthalpy

Outdoor air relative humidity

Return air temperature

Supply air temperature

Supply fan status

Unit status mode

Zone CO2

Zone relative humidity

Variable AirVolume (VAV) Points

Binary inputs

Airside economizer enable/disable

Condensor water flow input

Emergency override

Local fan switch enable/disable

Mechanical cooling lockout

Mechanical heating lockout

Occupancy

Binary outputs

Airside economizer status

Alarm status

Compressor on/off status

Condensor circuit information

Condensor type (water or air cooled)

Condensor waterflow status

Condensor water pump status

Analog inputs

Airside economizer dry bulb setpoint

Airside economizer minimum position

Building static pressure input

Building static pressure setpoint

Daytime warm up setpoint

Daytime warm up terminate setpoint

Maintenance required time

Occupancy bypass time

Outdoor air damp min position setpoint

Outdoor airflow minimum setpoint

Outdoor air relative humidity

Outdoor air temperature

Supply air cooling setpoint

Supply air cooling setpoint (default)

Analog outputs

Building static pressure status

Alarm message

Condensor saturated refrigerant temp.

Condensor water temperature

Condensor water temp (local)

Cooling output status

Exhaust fan status

Heating output status

Heating/cooling mode

Mixed air temperature

Morning warm up sensor temperature

Outdoor air damper position

Outdoor air enthalpy

Outdoor air flow

Outdoor air relative humidity status

Outdoor air temperature status

Return air temperature

70

SCXG-SVX01B-EN

Page 70
Image 70
Trane SCXG-SVX01B-EN general Operation information, Points List - RTM Module, Points List - GBAS Module, Binary inputs