Maintenance information

general

Maintenance information

Table M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data

 

 

Water-Cooled Units

 

 

Air-Cooled Units

 

Unit Size

20

25

30

35

20

25

32

Compressor Data

 

 

 

 

 

 

 

Quantity

2

2

1/1

2

2

1/1

2

NominalTon/Comp

10

10

10/15

15

10

10/15

15

Circuits

2

2

2

2

2

2

2

Evaporator Coil Data

 

 

 

 

 

 

 

Rows

2

4

4

4

3

4

4

Sq. Ft.

22.5

25.0

25.0

25.0

25.0

25.0

25.0

FPF

144

144

144

144

144

144

144

CondenserData

 

 

 

 

 

 

 

MiniumGPMw/oEcon

36

36

46

54

MinimumGPMw/Econ

41

41

60

65

MaximumGPM

80

80

102

119

Evaporator Fan Data

 

 

 

 

 

 

 

Quantity

2

2

2

2

2

2

2

Size (Dia. x width - inches)

125/ ”x8"

125/ ”x9"

125/ ”x11"

125/ x11"

125/ ”x8"

125/ ”x9"

125/ ”x11"

MinimumHP

8

8

8

8

8

8

8

5

5

5

5

5

5

5

MaximumHP

20

25

25

25

20

25

25

MinimumDesignCFM

6350

7250

7250

7250

7250

7250

7250

MaximumDesignCFM

8500

10,625

12,750

14,875

8500

10,625

13600

R-22 Refrigerant Data

 

 

 

 

 

 

 

EER

12.6

13.9

13.4

12.5

10.3

10.7

10.1

IPLV

13.2

14.1

12.9

12.2

11.4

11.4

10.4

Refrigerant Charge - lbs.

 

 

 

 

 

 

 

Circuit A

25

25

27

27

Circuit B

25

25

25

27

Capacity Steps - %

100/53/0

100/53/0

100/65/47/0

100/53/0

100/52/0

100/66/47/0

100/52/0

407C Refrigerant Data

 

 

 

 

 

 

 

EER

11.6

13.2

12.3

11.3

IPLV

12.3

13.5

12.2

11.5

Refrigerant Charge - lbs

 

 

 

 

 

 

 

Circuit A

23.5

23.5

26.5

26.5

 

 

 

Circuit B

23.5

23.5

23.5

26.5

 

 

 

Capacity Steps - %

100/53/0

100/53/0

100/65/42/6

100/53/0

 

 

 

Filter Data

 

 

 

 

 

 

 

Quantity

4

4

4

4

4

4

4

Size (inches)

(16x25x2)

(16x25x2)

(16x25x2)

(16x25x2)

16x25x2

16x25x2

16x25x2

Quantity

4

4

4

4

4

4

4

Size (inches)

20x25x2

20x25x2

20x25x2

20x25x2

20x25x2

20x25x2

20x25x2

CCRC/CIRC Condenser Match

20

29

32

Notes:

1.Compressors areTrane 3D® scroll.

2.EER and IPLV are rated in accordance to the ARI Standard 340/360-93 for large unitary equipment. Based on 80/67°F (26.7/19.4°C) to the evaporator coil, nominal airflow and 85-95°F (29.4- 35°C) condenser water.

3.All units operate with R-22. Units ships with full operating charge.

4.Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.

5.Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.

6.Filter sizes are for units without hot water or steam heating coils

Table M-GI-2. SCWG/SIWG/SCRG/SIRG Self-Contained Heating Coil Maintenance Data

Filter Data for Heating Coil

 

 

 

 

 

Quantity

4

 

 

 

 

Size (inches)

20x18x2

 

 

 

 

Size (mm)

(508x457x51)

 

 

 

Quantity

8

 

 

 

 

Size (inches)

20x20x2

 

 

 

 

Size (mm)

(508x508x51)

 

 

 

Coil Data

Type

Rows

No. - Size (in)

No. - Size (mm)

fpf

Steam Coil

NS

1

2 - 24 x 58

2 - 609.6x1473.2

42

Hot Water Coil

WC

1

2 - 24 x 58

2 - 609.6x1473.2

80

Notes: 1. Hot water and steam heating coils have Prima-Flo®fins and do not have turbulators. 2. For coil capacities, useTOPSS(Trane Official Product Selection Program). 3. Full capacity coils consist of two coils stacked and piped in parallel.

SCXG-SVX01B-EN

91