Electrical Requirements

Selection Procedures

RLA = rated load amps

Compressor LRA = locked rotor amps Fan motor LRA = locked rotor amps, N.E.C. table 430 - 150

FLA = full load amps, N.E.C. Table 430 - 150

Voltage utilization range is ±10%

Determination of minimum circuit ampacity (MCA).

MCA = 1.25 x largest motor amps/VFD amps (FLA or RLA) + the sum of the remaining motor amps.

Determination of maximum fuse size (MFS) and maximum circuit breaker size (MCB).

MFS and MCB = 2.25 x largest motor amps (FLA or RLA) + the sum of the remaining motor amps.

For units with the dual power option, there are two electrical circuits that need calculations using the formulas above: circuit #1 - fans

circuit #2 - compressors

If the rating value determined does not equal a standard current rating of over current protective device, use the next lower standard rating for the marked maximum rating.

Table ED-1. Number of Compressors per Unit

SCWG/SIWG 20

25

30

35

SCRG/SIRG

20

 

25

32

10 HP

2

2

1

-

15 HP

-

-

1

2

Table ED-2. SCWG/SIWG Compressor Motor Data

 

200V

 

 

460V

 

575V

HP

RLA

LRA

RLA

LRA

RLA

LRA

10

33.1

269

14.4

117

11.5

94

15

46.9

409

20.4

178

16.4

143

Table ED-3. SCRG/SIRG Compressor Motor Data

 

200V

 

 

460V

 

575V

HP

RLA

LRA

RLA

LRA

RLA

LRA

10

38.4

269

16.7

117

13.4

94

15

55.0

409

24.1

178

19.1

143

Table ED-4. Fan without VFD

HP

FLA

200V

FLA

460V

FLA

575V

LRA

LRA

LRA

5

16.1

105

6.7

46

5.4

37

7.5

25.0

152

10.8

66

8.2

54

10

32.9

193

14.2

84

11.4

66

15

44.8

290

20.3

126

16.2

102

20

61.0

373

25.0

162

20.0

132

25

74.0

469

31.0

204

24.2

162

Table ED-5. Fan with VFD

 

 

200V

 

460V

HP

FLA

LRA

FLA

LRA

7.5

13.8

152

10.6

66

10

32.2

193

14.2

84

15

48.3

290

21.0

126

20

61.9

373

27.6

162

25

78.2

469

34.0

204

Note:Values are at the maximumVFD input rating and not the reduced motor values.

Table ED-6. Electric Heat - Single Stage

SCWG/SIWG

SCRG/SIRG

Heat

200V

460V

Size

Size

Kw

Amps

Amps

20

20

16

44.8

19.6

25

25

20

55.6

24.2

30

-

24

66.8

29.0

-

32

26

72.4

31.6

35

-

28

78

34.0

Note: Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the unit in the heating mode will not exceed the current of the unit in the cooling mode.

Table ED-7. CCRC/CIRC Condenser Electrical Data

Unit Size

Rated

 

 

 

 

MFS/

Tons

Voltage

# Fans

FLA (ea.)

LRA (ea.)

MCA

MCB

20, 29, 32

200

4

4.1

20.7

17.4

20

 

230

4

4.1

20.7

17.4

20

 

460

4

1.8

9.0

7.7

15

 

575

4

1.4

7.2

6.0

15

Note: All motors for CCRC/CIRC units are rated at 1 hp (.7457 kW).

34

SCXG-SVX01B-EN

Page 34
Image 34
Trane SCXG-SVX01B-EN manual Selection Procedures

SCXG-SVX01B-EN specifications

The Trane SCXG-SVX01B-EN is an advanced variable refrigerant flow (VRF) system designed to provide efficient and flexible heating and cooling solutions for commercial and residential applications. This system exemplifies Trane's commitment to innovation, energy efficiency, and ease of installation, making it a standout choice in the industry.

One of the main features of the SCXG-SVX01B-EN is its ability to deliver precise temperature control across multiple zones. The system utilizes a modular design that allows for the connection of multiple indoor units to a single outdoor unit, enabling simultaneous heating and cooling in different areas of a building. This zoned comfort not only enhances occupant satisfaction but also contributes to energy savings by allowing for targeted climate control where it is most needed.

Trane's VRF technology is complemented by its inverter-driven compressors, which adjust their speed according to the demand for heating or cooling. This means that the system operates more efficiently than traditional systems by consuming less energy during partial load conditions. The SCXG-SVX01B-EN also integrates advanced heat recovery capabilities, allowing it to transfer heat from one zone to another, further optimizing energy usage.

The unit's compact design simplifies installation, making it suitable for both retrofit projects and new constructions. The flexible piping layout supports various configurations, allowing easy adaptation to the building's architecture. The model also incorporates intelligent controls, offering a user-friendly interface that enhances operational flexibility and promotes energy management.

In addition to its performance features, the Trane SCXG-SVX01B-EN emphasizes sustainability. It uses advanced refrigerants with low global warming potential (GWP), aligning with environmental regulations and helping to minimize the system's ecological footprint. The durable construction of the system ensures longevity and reliability, reducing maintenance costs and enhancing overall operational efficiency.

Finally, Trane supports its products with comprehensive warranties and a network of service professionals, ensuring that customers have access to expert assistance throughout the life cycle of their system. The SCXG-SVX01B-EN represents a blend of technology, efficiency, and versatility, making it an ideal choice for those seeking an effective heating and cooling solution.