Installation

Tank Gauge Transmitter

 

 

2.5Connecting the RTD

The following list shows how the ATT is wired to an RTD device. The ATT’s temperature circuit is designed to work with a platinum or copper 3-wire RTD.

2.5.1Connecting the Handheld Terminal

Figure 2-3 on page 6 shows how the 1200 Hand Held Terminal is connected to the ATTI bus on the ATT. The Model 268 can also be used to configure the ATT.

Warning! The 1200 Hand Held Terminal on the ATT is not Intrinsically Safe. Care must be taken to only use in a non-hazardous environment

Wire as follows:

Connect the RTD's A terminal to the ATT's terminal 6, A.

Connect the RTD's B terminal to the ATT's terminal 5, C.

Connect the RTD's C terminal to the ATT's terminal 4, C.

2.5.2Wiring Completion

Caution! Do not overtighten metal plugs used to seal wiring compartment ports. Overtightening may damage the housing.

Properly seal the 1/2-inch NPT conduit entry. Install cover and tighten to ensure that the O-ring seal is adequately compressed. Proper sealing of all ports is necessary to prevent moisture or other contamination from entering the wiring compartment.

2.5.3Installation Checkout

After a thorough check that all connections are correctly made and that all covers and plugs are installed, turn on power to the ATT. Proceed to Chapter 3, Configuration.

2.5.4Installation Checklist

The steps required in the installation process are summarized in the following checklist. Since each step is detailed specifically with accompanying notes, cautions, and warnings, be sure to refer to the sub-sections indicated for further information.

 

Step

Sub-Section(s) Reference

 

 

 

 

Unpack the ATT and check the packing list.

Unpacking

 

 

 

 

Verify that the required input power is available.

Mounting the ATT, Wiring

 

 

 

 

Mount the ATT.

Mounting the Equipment

 

 

 

 

Ground the ATT.

Grounding the Equipment

 

 

 

 

Route the conduit between the ATT and other

Wiring Completion

 

devices and seal all ports.

 

 

Wire the host communications.

Connecting Host Communication

 

 

 

 

Wire the RTD

Connecting the RTD

 

 

 

 

Wire the input power connections.

Connecting Input Power

 

 

 

 

Apply power to the ATT.

Installation Checkout

 

 

 

 

Wire the Model 1200 Handheld Terminal

Connecting Handheld Terminal

 

 

 

 

Proceed to ATT configuration procedure.

ATT Configuration (Section 3)

 

 

 

10

Installation and Operations Manual

Page 20
Image 20
Varec 4000 manual Connecting the RTD, Connecting the Handheld Terminal, Wiring Completion, Installation Checkout