Varec 4000 manual Model 4050 Digital Input/Output Unit, Digital Outputs, Digital Inputs

Models: 4000

1 78
Download 78 pages 61.23 Kb
Page 54
Image 54

ATT Family of Products

Tank Gauge Transmitter

 

 

8.2Model 4050 Digital Input/Output Unit

The Model 4050 is a digital I/O unit. It includes four digital contact closure outputs and four digital inputs. It operates connected to and is powered from the ATTI bus. The unit is mounted in a round explosion proof junction box. Three 3/4-inch conduit entries are available.

Primarily configured by jumpers. Three sets of jumpers are used.

Unit address: 4 jumpers for range 0-15. Digital I/O units normally use address 4,5 or 6.

Active state jumper for each digital output. Jumper determines if contact is N. O. or N. C.

Default power condition for each digital output. Jumper determines if contact is open or closed when no power is applied.

8.2.1Digital Outputs

The use of the digital outputs is configured within the ATT using the handheld interface. Digital outputs 1 - 4 can be configured as follows:

1.Set output as level switch:

Set for low or high closure.

Set level to actuate.

2.Set output for Modbus command to write.

8.2.2Digital Inputs

Digital inputs 1 - 4, can each be read with a Modbus command.

8.2.3Relay Specifications

The latching relays will switch 110 VAC at 1 A or 24 VDC at 2 A. The unit does not support 220/230 VAC.