4000 | Installation |
|
|
2.4.6ATT Mark/Space Wiring
For an ATT using the Mark/Space field communications option, the following additional wiring connections must be made. (Refer to Input Power Wiring in Section 6 to determine the minimum wire size required.). See Figure
•Run two twisted pairs of 18 AWG wire (Mark/Space wires) into the ATT through the conduit entry along with the 48 VDC power wiring.
•Connect the Mark line to terminal 11,
8203 With 8210 expansion module
Field Junction Box
4 Conductor
Cable
18 AWG
Shielded
To Other
Transmitters
in Area 0
Ground shield at RTU8130 ONLY!
Do NOT ground shield at transmitter.
External
Power Supply
Varec
Model 4000
ATT
Details of RTU8130 with 8210 expansion module and ATT termination board wiring
Figure 2-6: Typical Mark/Space Field Wiring
9