Modbus Implementation

Tank Gauge Transmitter

 

 

Note! In all of the following communication examples, the error check value is dependent upon the mode of transmission.

9.5.1Integer Data

The integer data is a whole number between 0 and the maximum Modbus integer (inclusive). The maximum Modbus integer is a user-configurable variable that is a whole number between 0 and 65,535 (inclusive). The integer data must also be scaled for each data type by entering the desired units, a minimum, and a maximum value. In order for the integer value to be correctly interpreted, these scaling factors must match the format expected by the host system. Scaling of the integer parameters is accomplished through floating-point registers or by using the Model 1200 Handheld Interface.

The following communication example shows the request for one register starting at register 0 (0000 Hex).

For the following example, assume:

minimum = 1 meter

maximum = 15 meters

maximum Modbus integer = 65,534

Host Request

Address

Function

Start Reg

Start Reg

# of Reg

# of Reg

Error

 

Code

H

L

H

L

Check

 

 

 

 

 

 

 

01

03

00

00

00

01

XX

 

 

 

 

 

 

 

ATT Response

 

 

 

 

 

Address

Function

Byte

Data

Data

Error

 

 

code

Count

MSB

LSB

Check

 

 

 

 

 

 

 

 

01

03

02

41

24

XX

 

 

 

 

 

 

 

 

48