ELECTRICAL CONNECTION

ELECTRICAL CONNECTION

WARNING: ELECTRICAL AND GROUNDING CONNECTIONS MUST COMPLY WITH APPLICABLE PORTIONS OF THE NATIONAL ELECTRICAL CODE AND/OR OTHER LOCAL ELECTRICAL CODES.

WARNING: DISCONNECT THE ELECTRICAL POWER SUPPLY FROM THE OVEN AND FOLLOW LOCKOUT / TAGOUT PROCEDURES.

The wiring diagram is located on the inside surface of the right side panel as you face the oven. Use copper wire rated for at least 90°C for the connection.

 

ELECTRICAL DATA

 

 

 

 

 

 

BRANCH CIRCUIT SIZE

 

 

AND PROTECTION

Model

Volts / Hz / Ph

 

Minimum Circuit Ampacity

 

 

 

 

Maximum Protective Device

 

 

AMPS

 

 

 

 

208 / 60 / 3

35

VCE6H

240 / 60 / 3

30

 

480 / 60 / 3

15

 

 

 

VCE10H

208 / 60 / 3

70

VCE10F

240 / 60 / 3

60

480 / 60 / 3

30

 

 

 

 

208 / 60 / 3

90

VCE20H

240 / 60 / 3

80

 

480 / 60 / 3

40

 

 

 

 

208 / 60 / 3

125

VCE20F

240 / 60 / 3

110

 

480 / 60 / 3

60

 

 

 

Compiled in accordance with the National Electrical Code, ANSI/NFPA 70, latest edition.

NOTE: Only single-phase fan motors are used on these ovens so there is no need to check direction of motor rotation. The fan will rotate in the proper direction.

VENT HOOD

Some local codes may require the Combi oven to be located under an exhaust hood. Information on the construction and installation of ventilating hoods may be obtained from Vapor Removal from Cooking Equipment, NFPA standard No. 96 (latest edition).

BEFORE FIRST USE

Before using the oven for the first time, it must be "burned in" to release any odors that might result from heating the new surfaces in the oven. Operate the oven at 480°F for 45 minutes in Convection HOT AIR Mode. Depending on which control is furnished, perform CONFIGURATION MODE — PROGRAMMABLE CONTROL on pages 36 – 37 or CONFIGURATION MODE — MANUAL CONTROL on pages 38 – 39.