VL SERIES STEAMERS - GENERAL
COOKING COMPARTMENT CONTROLS
The top half of the steamer consists of two to three separate cooking compartments depending on the model. Each compartment functions independently with its own set of controls. Power is supplied to the controls through the compartment power switch and the cooking timer control micro switch contacts. Prevent and Automatic models have a load compensating thermal switch that prevents the controls from receiving power until the compartment reaches 180°F to close the switch.
Compartment Power Switch | Supplies power to the cooking compartment controls. |
Cooking Light (Red) | When lit, indicates steamer is in a cooking cycle. (All models except |
| manual) |
Cooking Timer | Use to set desired cooking cycle time between |
| the buzzer when time expires (All models except manual). On Prevent |
| models, also |
| before the end of a cook cycle to allow compartment venting. |
Buzzer | Signals end of a cook cycle, must be turned off manually. (All models |
| except manual) |
Steam Exhaust Solenoid Valve . . . | A normally open valve that allows full compartment venting of air and |
| condensate up to 180°F durin g compartment heat up and “limited free |
| venting” after energized by the closing of the thermal switch. The valve |
| remains closed to allow compartment pressurization to 6 psi until one |
| minute before the end of a cook cycle at which point the timer control |
| micro switch contacts (SW2) change state and |
| vent the compartment of pressure and steam. (prevent models) |
Steam Header Inlet (manifold) . . . . | Main steam supply line from the boiler for each cooking compartment. |
| Supplies steam to the manual steam gate valves. |
Compartment Pressure Gauge . . . . | Indicates the amount of steam pressure in cooking compartments. |
Steam Control Arm Solenoid | When energized, engages the lift arm (plunger) to raise the steam |
| control arm off of the catch, allowing it to return to its rear position. This |
| closes the steam inlet gate valve and opens the steam exhaust gate |
| valve. (prevent, automatic and standard models) |
Thermal Switch |
|
(Load Compensator) | Controls power to the preheat cycle components. Turns the cooking light |
| on, energizes the steam exhaust solenoid valve and energizes the |
| cooking timer motor to start timing, after the compartment reaches |
| 180F. (prevent and automatic models) |
Steam Gate Valves | Manual valves actuated by the steam control arm. Allows steam to flow |
| into the cooking compartment through the inlet steam gate valve when |
| the arm is in a forward position and exhaust the steam through the |
| exhaust steam gate valve when the arm is at the rear. Prevent models |
| use a steam exhaust solenoid valve to exhaust the steam and a single |
| steam gate valve as the steam inlet. The automatic, standard and |
| manual models use one steam gate valve to exhaust the steam and |
| one additional steam gate valve as the steam inlet. |
Steam Trap (Condenser) | Exhausts air and condensate from compartment during preheat until the |
| compartment temperature reaches approximately 180F. The bellows |
| then close, stopping the exhaust. (all models except prevent) |
Page 13 of 88