GOLD CGi
4c Water piping — multiple zones
Piping multiple zones
Follow instructions on pages 20 and 21 to install near-
boiler or
tems, below, if applicable.)
See Figure 18 or Figure 19 to complete installation.
Zoning with circulators (Figure 18) (return temp over 130°F)
1.Size each circulator to individual circuit require- ments.
2.Do not install circulator on boiler (except for pri- mary/secondary piping).
3.Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
4.Install and wire a separate relay for each zone cir- culator.
Zoning with zone valves (Figure 19) (return temp over 130°F)
1.Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
2.Provide a separate
Piping for radiant heating systems or converted gravity systems
Converted gravity (or steam) systems
Whenever possible, use the primary/secondary piping shown in Figures 20 or 21 on page 25. This piping de- sign allows changing boiler flow rate without affecting primary circuit flow rate.
If Figures 20 or 21 cannot be used, use the
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sec- tions or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in Figures 20 or 21 on page 25. Alternatively, use the method of either Figure 22 or Figure 23 on page 27. Do not use the piping of Figure 24
If radiant system tubing has no oxygen barrier, a heat exchanger must be used.
Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control). Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods in this manual if the system is equipped with an outdoor reset control. Instead, provide controls and piping which can regulate the boiler return water temperature at no less than 130°F regardless of system supply temperature. Contact your
22 | Part Number |
|