GOLD CGi Gas-Fired Water Boiler — Boiler Manual

4c Water piping — multiple zones (continued)

Figure 18 Zoning with circulators

Figure 19 Zoning with zone valves

— return water 130°F or higher.

— return water 130°F or higher.

1

Boiler isolation (balancing) valves

10

Automatic air vent (with diaphragm-type expansion tank), or con-

 

 

 

nect to tank fitting (closed-type expansion tank). DO NOT use an

2

Flow/check valve

 

automatic air vent when using closed-type expansion tank. It would

 

allow air to leave the system, causing waterlogging of the expansion

 

 

 

3

System or zone circulator

 

tank.

11

Fill valve

 

 

5

Zone valve

12

Diaphragm-type or bladder-type expansion tank, if used (For

 

 

 

closed-type expansion tank, pipe from top of air separator to tank

6

Drain valve

 

fitting as in Figure 17.)

9

 

13

Air separator and automatic vent, if used (Note that the fill valve

Relief valve

 

must always be connected to the expansion tank, regardless of loca-

For systems with possible low return-water temperature (such as converted gravity systems, radiant heating systems and heat pump systems), refer to the special piping suggestions of Figures 20 – 24, as applies. Failure to prevent sustained low return water temperature to the boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death or substantial property damage.

Part Number 550-110-710/0107

23

 

Page 23
Image 23
Weil-McLain 550-110-710/0107 manual Zoning with circulators