GOLD CGi
11c Troubleshooting — control module lights (cont.)
CHART 7 — Insufficient heat or no heat to system (POWER light on steady)
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Has it been at least 5 minutes since setting thermostat to call for heat? If not, wait 5 minutes. Is system heating?
•Is thermostat set to call for heat? Remove thermostat wires at boiler and check continuity across the two wires. If circuit isn't closed, check external thermostat (zone valve, relay, etc.) wiring. Correct problems and retry.
•Reconnect external thermostat wiring at boiler.
Is thermostat circuit closed (continuity across wires)?
|
| No |
|
| Yes | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • Boiler is in standby. | ||
|
|
|
|
|
| |||
Are all red lights off? |
| • | Set thermostat to call for | |||||
|
|
|
|
|
|
| heat and recheck | |
No |
| Yes |
|
|
| |||
|
|
|
| operation. | ||||
|
|
| ||||||
|
|
|
|
|
| • | Verify Sequence of | |
|
|
|
|
|
| |||
Wait 30 seconds. |
|
|
| operation, Figure 30, | ||||
|
| page 37. | ||||||
Are all red lights off? |
|
|
| |||||
|
|
|
| |||||
|
|
|
|
|
|
| ||
No |
| Yes |
|
|
|
|
| |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
Replace control module. Retest.
•If you have sufficient heat — boiler should be in normal operating sequence. (See normal sequence of operation, Figure 30, page 37.)
•If you have less than sufficient heat —
Is vent piping free of blockage?
| No |
|
| Yes | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• | Correct conditions and |
| • | Check heat loss | ||
| recheck operation. |
|
| calculation versus boiler | ||
• | See Figure 30, page 37 |
|
| size. | ||
| for normal sequence of |
| • | Clock gas input. | ||
| operation. |
|
|
|
| |
|
|
|
|
| ||
|
|
|
|
|
|
|
•Wait for boiler water to cool to temperature 20 to 30 °F lower than temperature set on limit switch.
Are limit switch contacts closed?
| No |
|
| Yes |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • Boiler water temperature exceeded | |||
|
|
|
| setting on limit switch with thermostat | |||
|
|
|
| ||||
• | Replace |
| calling for heat. Boiler is OK. (See normal | ||||
| sequence of operation, Figure 30, p. 37.) | ||||||
| limit switch. |
| |||||
|
| • Also check setting on limit switch (should | |||||
• | Retest. |
| |||||
| be above 140°F.). | ||||||
|
|
|
| ||||
|
|
|
|
|
|
|
|
Is boiler System circulator operating?
No | Yes |
|
|
•Remove CIRCULATOR harness plug from CIRCULATOR plug receptacle (Figure 38,
Item 7, page 50). Check with voltmeter across pins of control module receptacle.
Does voltmeter show 120 VAC across pins?
|
|
|
| No |
|
|
|
|
|
|
|
|
|
| Yes |
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • | Replace control |
| • | Repair/replace |
|
|
| ||||||||||||||||||
|
|
| module. |
|
|
|
|
|
| circulator. Retest. |
|
|
| ||||||||||||||
|
| • | Retest. |
|
|
| • | Repair/replace |
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| wiring. Retest. |
|
|
| |||||||||
• |
| Wait 5 minutes. |
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
| Is FLAME light on? |
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
| No | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| Is LIMIT light on? |
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| No |
|
|
|
|
|
|
|
|
|
|
|
|
| Yes | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• |
| Check limit switch |
|
|
|
| • | Replace control module. | |||||||||||||||||||
|
| contacts with continuity |
|
|
|
| • | Retest. | |||||||||||||||||||
|
| checker. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| Are limit switch contacts |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
| closed? |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check rollout switch | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
| No |
|
|
| Yes |
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| continuity — is switch | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| closed? | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| No |
|
| Yes | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• |
| Replace rollout switch. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • | Check any other | ||||||
If rollout thermal fuse element has |
|
| |||||||||||||||||||||||||
|
|
|
| limit controls wired | |||||||||||||||||||||||
opened, determine cause and |
|
|
|
|
|
|
| into the limit | |||||||||||||||||||
correct condition. Failure to do so |
|
|
|
| circuit. If all are | ||||||||||||||||||||||
will cause severe personal injury, |
|
|
|
| OK, then replace | ||||||||||||||||||||||
death or substantial property |
|
|
|
|
|
|
| control module. | |||||||||||||||||||
damage. |
|
|
|
|
|
|
|
|
|
|
| • | Retest. |
Part Number | 57 |
|