GOLD CGi
3f Venting — direct exhaust — installation
1. Do not mix types or manufacturers of vent materi- | Figure 13 Direct exhaust vertical venting | |
als. | ||
| ||
2. Clean all joints before sealing. See vent manufactur- |
| |
er’s instructions for cleaning and sealing joints. Use |
| |
their specified sealant. Do not use screws. |
| |
3. Install vent pipe with seams on top of vent horizon- |
| |
tal runs. Follow requirements in Section 3e for vent |
| |
termination. |
| |
4. Maintain minimum 2” clearance from combustible |
| |
materials to vent pipe. |
| |
5. Vertical venting — See Figure 13. Follow vent |
| |
manufacturer’s instructions for venting through |
| |
roof. |
| |
• Vent pipe must extend through roof flashing, |
| |
jacket or thimble. |
| |
• Vent may pass through floor, inside wall or |
| |
concealed space when installed according to |
| |
vent manufacturer’s instructions. |
| |
Sidewall venting — See Figures 14 and 15. |
| |
Vent must terminate at least one foot above |
| |
anticipated snowline. Vent must be terminated |
| |
only with: |
| |
• Tee or elbow with integral screen. (Tee may be |
| |
mounted either vertically or horizontally. DO |
| |
NOT use horizontal tee with |
| |
• Elbow and termination coupling with screen |
| |
(not available for |
| |
6. Do not seal vent pipe (slip connector for |
| |
to inside or outside plate. |
| |
7. If passing through noncombustible wall, provide |
| |
hole diameter large enough to insert the vent pipe |
| |
Figure 14 Direct exhaust sidewall venting | ||
(slip connector for | ||
| ||
8. Install horizontal drain tee as close as possible |
| |
to boiler, in first horizontal run. See Figures 13 |
| |
and 14. |
| |
9. Do not exceed the maximum vent system length |
| |
given in Table 4, page 15. |
| |
Condensate drain line — use only silicone tubing rated |
| |
for at least 400°F for the first 18” of condensate drain |
| |
line, then other |
| |
ing any other material could cause flue gas leakage, |
| |
potentially resulting in severe personal injury, death or |
| |
substantial property damage. |
|
On some installations, the condensate drain fitting may be omitted, provided:
•Vent manufacturer shows this option in their instruc- tions.
•Vent is sloped toward termination as shown in dotted lines in Figure 14.
•The vent is installed per
•Condensate drippage from such vents may accumu- late on the ground below. Consider traffic in the area to avoid hazard due to ice accumulation.
18 | Part Number |
|