Introduction
1–4 973-0031-01-01 Rev A
Specifications

The following table contains the specifications for the ACCB-L, the ACCB-L-L1,

and the ACCB-L-L2. The ACCB-L-L2 is not available pre-built from the factory,

but is created by field-installing an ACCB-L2-PCK into a ACCB-L-L1 model.

Table 1-1

Operational and Environmental Specifications for the ACCB-L, ACCB-L-L1, and ACCB-L-L2

ACCB-L ACCB-L-L1 ACCB-L-L2a
Dimensions 33" (H) x 11" (W) x 8 3/4" (D)
(84 cm x 28 cm x 23 cm)
33" (H) x 11" (W) x 8 3/4" (D)
(84 cm x 28 cm x 23 cm)
This configuration is created
by field-installing an ACCB-
L2-PCK into an ACCB-L-
L1.
Weight 19 pounds (8.6 kg) 24 pounds (10.9 kg) ~2 pounds
Shipping Weight 23 pounds (10.4 kg) 27 pounds (12.2 kg) ~2 pounds
Operating Voltage 120/240 Vac,
60 Hz split-phase
120/240 Vac,
60 Hz split-phase
120/240 Vac,
60 Hz split-phase
Factory-installed
hardware
• Din Rail
• Ground Bar
• Din Rail
• Ground Bar
• AC Bus Bar (Neutral)
• AC Bus Bar (HOT L1)
• AC Input/Output Terminals
• AC Bypass Breaker
• Din Rail
• Ground Bar
• AC Bus Bar (Neutral)
• AC Bus Bar (HOT L1)
• AC Input/Output
Term inals
• AC Bypass Breaker
Factory-installed
wiring
None #6 THHN AWG, rated to
105 °C, stranded copper
• One - Ground Wire
• One - Neutral Wire
• One - HOT IN
• One - HOT OUT
#6 THHN AWG, rated to
105 °C, stranded copper
• One - Ground Wire
• One - Neutral Wire
• One - HOT IN
• One - HOT OUT
Field-installed
hardware
N/A ACCB-L2-PCK (needed to
create ACCB-L-L2)
• AC Bypass Breaker (Din
Rail-mountable) (w/HOT In
and HOT Out wiring)
• AC Bus Bar (HOT L2)
AC Bypass Switch
Bypass None 60 Amp (SPST) 60 Amp (SPST)
Inverter
Input/Output
None 60 Amp (DPST) 60 Amp (DPST)
Rated Temperature 0 to 25 °C
(32 to 77 °F)
0 to 25 °C
(32 to 77 °F)
0 to 25 °C
(32 to 77 °F)
Storage
Temperature
-55 to +100 °C
(-67 to 212 °F)
-55 to +100 °C
(-67 to 212 °F)
-55 to +100 °C
(-67 to 212 °F)
Enclosure Indoor rated, White,
Powdercoat Finish
Indoor rated, White,
Powdercoat Finish
Indoor rated, White,
Powdercoat Finish