SECTION 1

PRODUCT DESCRIPTION

SPECIFICATIONS

The PV-225208 has been designed for photovoltaic power systems, which operate within the following speci- fications.Application of the PV-225208 in a manner inconsistent with these specifications may cause damage to the PV-225208 and other system components, and is a violation of the terms of the warranty.

Nominal AC Line Voltage

208

VAC, +10% -12%

 

 

 

Maximum AC Line Current

695

ARMS (at low line voltage)

 

 

Nominal Line Frequency

60 Hz, +0.5 -0.7 Hz

 

 

Continuous AC Output Power

225.0 kW @ 208 VAC 3 Phase

PV Maximum Voltage

600

VDC

 

 

Peak Power Tracking Window

330*-600 VDC

 

 

 

PV Minimum Peak Power Tracking Voltage

330

VDC

 

 

PV Maximum Operating Current

710 ADC

Maximum PV Array Short Circuit Current

1100 ADC

PV Configuration

Monopolar negative grounded

 

 

Operating Temperature

**-20 to 50° C

 

 

Storage Temperature

-40 to 50° C

 

 

Maximum Ambient Temperature Rating

50° C

 

 

Relative Humidity

To 95%, Non-condensing

 

 

Elevation

Derated above 6,600 feet

Dimensions (in inches)

87 X 102 X 27

 

 

Weight

Approx. 1935 lbs.

 

 

Enclosure Type

NEMA 3R

 

 

UL Listing File

File-E199356

 

 

 

*Dependent on actualAC line voltage. Refer to Section 4 for detail on the minimum power tracking voltage. **If ambient temperature is between -20 to 0° C, the unit must be powered up in standby for at least one hour prior to going on-line.

EQUIPMENT SYMBOL

Chassis ground – Customer supplied system ground connection point. This symbol may be found near a stud within the main enclosure. It is provided as a location to bond the electrical system equipment ground.

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

1-4

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Page 6
Image 6
Xantrex Technology PV-225208 important safety instructions Section Product Description Specifications, Equipment Symbol