
SECTION 5
TROUBLESHOOTING
The dry contact auxiliary switch mounted to the PV disconnect switch has been toggled. The auxiliary switch should be opened when the PV disconnect switch is open. If the fault will not clear when the PV disconnect switch is closed:
•Isolate
•Close PV disconnect switch and check continuity between PCU
XX25/XX26 - Line Gate Drive Fault (S)
One of the IGBT gate drive boards signaled the PCU that there was a fault. The second two digits refer to which matrix has the fault. XX25 refers to matrix 1 and XX26 refers to matrix 2. The particular device at which the fault was detected is indicated by the first two digits of the fault code, as follows:
XX: 01 = Phase A+ | 02 = Phase A- |
04 = Phase B+ | 08 = Phase B- |
10 = Phase C+ | 20 = Phase C- |
If more than one phase faults simultaneously, the error code will contain the summation of phase fault values. For example, if phaseA+ and B+ of matrix 1 fault simultaneously, the error will read 0525.
Make sure the fiber optics for the device and matrix in question are properly connected to the driver board. Similarly, make sure the fiber is properly connected at the PCU.
Clear the fault and restart the
YY27/YY28 - Line Over-Current Fault (S)
Current in one phase of the matrix has exceeded the allowable limit. YY27 refers to matrix 1 and YY28 refers to matrix2. The faulted phase is indicated by the first two digits of the fault code, as follows:
YY:01 = Phase A
02 = Phase B
04 = Phase C
If more than one phase faults simultaneously, the error code will contain the summation of phase fault values. For example, if phaseAand C of matrix 1 fault simultaneously, the error will read 0527.
Possible causes:
•AC system wiring short: Inspect the AC power system for short circuits.
•PCU Power Supply is defective: Verify
PCU. There are labeled test points on the PCU circuit board. Note: There are two isolated +15Vdc power supplies labeled +15Vdc and +15Vdc Drv. The +15Vdc Drv power supply provides power for the matrix driver boards only.
•Faulty CT wiring: Verify the wiring between the PCU power supply and the CT is properly con- nected and undamaged. Refer to page 2 of the system schematic in Section 7.
•CT defective: Locate the current transducer for the matrix and phase in question (see control com- ponents drawing in Section 7). With a digital
DOCUMENT: 151811 | ||
| Operation and Maintenance Manual |
|
Copyright 2003, Xantrex Technology Inc.