SECTION 6
PREVENTATIVE MAINTENANCE
PERIODIC MAINTENANCE
Xantrex Technology recommends that the following preventative maintenance be carried out on the
Monthly intervals or as required:
NOTE
Visually inspect the exterior surfaces for any damage (nicks, chips, exposed base metal and scratches). Touch up or recoat using White NISSEN Feltip Paint Marker, or equivalent to prevent rust or corrosion.
Aluminum Extrusion Heatsink
Accumulation of dirt and debris on the aluminum extrusion heatsinks and fans will decrease the ability to transfer heat, which can cause the
Fan Operation
Verify proper operation of the heatsink cooling fans, located above the matrix heatsinks. The fans operate when the K1 contactor is closed. Remove any debris from the fans.
Internal Circulation Fan:
Verify the internal circulation fan is operating whenever there is utility power applied to the
Inductor Enclosure Cooling Fans:
Verify these fans operate whenever the
Six month intervals:
(See Isolation Procedure located on page
Enclosure Seals
Inspect the enclosure access panel seal. If damaged, replace with equivalent closed cell foam gasket. Call your Xantrex Technology distributor for factory replacements or specifications.
Electrical Connections
Inspect the condition of all wiring within the