SECTION 2
SAFETY
Over/Under Voltage and Frequency
The over/under frequency and voltage detection setpoints have been chosen to be in compliance with
Fault Condition | Voltage Range | Trip Time | |
(% of Nominal) | |||
|
| ||
|
|
| |
VAC < 50% | VAC < 104 | 6 Cycles | |
|
|
| |
50% < VAC < 88% | 104 < VAC < 183 | 2 Seconds | |
|
|
| |
88% < VAC < 110% | 183 < VAC < 228 | Normal Operation | |
|
|
| |
110% < VAC < 137% | 228 < VAC < 285 | 2 Seconds | |
|
|
| |
137% < VAC | 285 < VAC | 2 Cycles | |
|
|
| |
f < rated | f < 59.3 | 6 Cycles | |
|
|
| |
f > rated +0.5 | f > 60.5 | 6 Cycles | |
|
|
|
Anti Island Protection
A digital
The DSP continuously makes minor adjustments to the power factor phase angle above and below unity. In the event of a utility outage, these adjustments destabilize the feedback between the inverter and the remaining load, resulting in an over/under frequency or voltage condition. The
This method has been extensively tested and proven to exceed the requirements of UL 1741.
ISOLATION PROCEDURE
The following procedure should be followed to
WARNING
The terminals of the PV input may be energized if the arrays are energized. In addition, allow 5 minutes for all capacitors within the main enclosure to discharge after disconnecting the
1.Turn the on/off switch to the off position.
2.Open the DC interface (PV array) disconnect switch.
3.Open the AC interface disconnect switch.
4.Open the isolation transformer circuit breaker.
5.Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.
DOCUMENT: 151811 | ||
| Operation and Maintenance Manual |
|
Copyright 2003, Xantrex Technology Inc.