SECTION 5
TROUBLESHOOTING
0063 - AC Voltage Too Low (S)
TheAC Inverter voltage fell below the minimum programmed limit (MinAC Volt).
This problem was caused by the utility. Clear the fault and restart the
Possible causes:
•High momentary load which forces the inverter to current limit
•Fuses F1, F2, F3, F4, F5 or F6 blown
•
•Contactor K1 inoperable
•Utility voltage fell below the allowable limit.
This fault is
0064 - AC Voltage Too High (S)
The inverter controller voltage exceeded the
Possible causes:
•
•Contactor K1 inoperable
•Utility voltage exceeded the allowable limit.
This fault is
012A - Interrupt Time-Out (S)
The PCU was not able to service the interrupt for approximately 1 second.
Attempt to clear the fault and restart the
0230 – Door Interlock Switch Open (H)
The door interlock lock switch located in the inside upper left corner of the main enclosure door is open.
If the switch is closed and the fault still registers on the front panel, isolate the
•Verify continuity across the switch contact block while the switch is closed.
•Verify continuity between
0430 - PV Auxiliary Switch Open (H)