SECTION 4
OPERATION
The user should be aware of the following conditions governing
•Utility power must be present for all states of operation.
•Fault states are automatic from any state of operation. A fault will cause the
•Most
•The On/Off switch, located on the front door of the
OPERATION FEATURES
Fixed Unity Power Factor Operation
The Xantrex PV Series grid tied inverters maintain unity power factor during operation. The control software constantly senses utility voltage, and constructs the output current waveform to match the utility voltage. The PV line of inverters are not capable of operation without the presence of normal utility voltage, nor are they capable of varying the output power factor off unity.
Utility Voltage/Frequency Fault Automatic Reset
In the event of a utility voltage or frequency excursion outside of preset limits, the
Active Island Detection
Much concern has been given to the possibility of an inverter causing a ‘utility island’ condition during a utility power outage. An island condition is defined as grid tied inverter maintaining operation and supporting a load that has been isolated from the utility power source. This requires the load to be closely balanced to the output power of the inverter as well as having a resonant frequency close to 60Hz. Needless to say, this is an extremely remote possibility. To insure this condition does not occur, the
Ground Fault Detection
The