Installation
| All wiring and installation methods should conform to applicable |
| electrical and building codes. |
Conduit holes | |
| located on the bottom of the unit. See Figure |
Acceptable wire | The DC terminal blocks in the Sun Tie XR accept up to a #6 AWG wire. |
sizes | The AC circuit disconnects accept cable sizes up to #6 AWG. |
| For maximum safety, run AC and DC wires/cables in separate conduits. |
WARNING: SHOCK HAZARD
Check for existing electrical or plumbing prior to drilling holes in the walls.
Planning AC Connections
AC connections include all the wires and connectors between the Sun Tie XR AC output breakers and the main utility electrical panel. Figure
Recommended wire sizes
The AC output breakers accept wire sizes from
Table
|
|
| Minimum wire size for specified distance | ||
|
|
|
|
|
|
| AC amps | NEC amps per leg | |||
Inverter model | output per leg | (amps x 125%) | one way | one way | one way |
|
|
|
|
|
|
STXR1500 | 6.3 | 7.9 | 14 AWG | 10 AWG | 8 AWG |
|
|
|
|
|
|
STXR2500 | 10.4 | 13.0 | 12 AWG | 8 AWG | 6 AWG |
|
|
|
|
|
|
Note: The