| Installation |
Connecting DC Wiring | |
Fuse requirements | The combiner board in the Sun Tie XR accepts up to six individual PV |
| array circuits (positive and negative wires). Each circuit on the combiner |
| board contains a fuse to protect against |
| fuse with one of the same type and rating (GBB, 20 amp maximum, |
| ceramic type, 0.25" x 1.25"). The combiner board is rated for 100 amps |
| maximum input. |
Combiner board | The combiner board PV array input connection block is located in the |
location | lower |
Wiring procedure | Before connecting DC wiring, refer to Figure |
PV array wiring to | ||
terminal block | + | |
(note polarity) | ||
| ||
| – |
PVGFP (ganged)
100 amp DC breaker
PVGFP (ganged) 1 amp DC breaker
PV array
100 amp DC breaker
L1 15 amp AC breaker (ganged)
L2 15 amp AC breaker (ganged)
L2 breaker AC
connection
L1 breaker AC connection
Ground bar
Figure
1.Install the DC conduit from the PV arrays to the bottom of the
Sun Tie XR, through one of the knockout holes, as shown in Figure 2- 9. Metal conduit is highly recommended.
2.Route the wires from the PV array(s) through the conduit and into the lower section of the Sun Tie XR enclosure, as shown in Figure
Note: If you are using more than one PV
3.Connect the positive (+) wire from the #1 array to the PV PLUS 1 terminal on the combiner board. Check that the wire is in the proper location and tighten the screw.