Installation Planning
AC circuit breaker requirements
The main service panel must dedicate a 15 amp minimum, double pole breaker (120/240 volts AC) to operate the Sun Tie XR.
Planning DC Connections
| DC connections include all the wires and connectors between your PV | ||||
| array and the Sun Tie XR’s combiner board. Figure | ||||
| show the combiner board and connection points. Figure | ||||
| |||||
Wire Sizes | The DC connections are made on the combiner board inside the | ||||
| Sun Tie XR. The combiner board accepts wire sizes from | ||||
| Refer to Table | ||||
Exceptions | The values in Table | ||||
| Installing a large number of wires in conduit or enclosed locations may | ||||
| require larger wire sizes. Consult your local or national electrical code for | ||||
| more information. |
|
|
| |
NEC Restrictions | The National Electrical Code (NEC) places restrictions on minimum DC | ||||
| wire bending radius. A #6 AWG wire is the largest that may be used on | ||||
| the Sun Tie XR when connecting to the individual fused circuits of the | ||||
| combiner board. |
|
|
| |
Table |
|
|
| ||
|
| Minimum wire size for specified distance | |||
|
| ||||
DC amps (Imp) |
|
|
|
|
|
NEC amps | |||||
(from PV array) | (amps x 156%) | one way | one way | one way | |
|
|
|
|
|
|
1.0 | 1.6 | 14 AWG | 14 AWG | 14 AWG | |
|
|
|
|
|
|
3.0 | 4.7 | 14 AWG | 12 AWG | 10 AWG | |
|
|
|
|
|
|
5.0 | 7.8 | 12 AWG | 10 AWG | 6 AWG | |
|
|
|
|
|
|
7.0 | 10.9 | 12 AWG | 8 AWG | 6 AWG | |
|
|
|
|
|
|
9.0 | 14.0 | 10 AWG | 8 AWG | Not Recommended | |
|
|
|
|
|
|
11.0 | 17.2 | 10 AWG | 6 AWG | Not Recommended | |
|
|
|
|
|
|
Note: For an installation requiring a