Installation
L1
240 VAC
L2
Ground bar
| Figure |
Grounding the System | |
PV grounding | The Sun Tie XR is designed to have all PV positive, negative and ground |
| conductors connected inside its access area. The PV equipment ground |
| should be connected to the Sun Tie XR ground bar. This ground bar must |
| also be connected to the main utility breaker panel’s ground bar and to the |
| house grounding rod according to the NEC requirements. Verify that there |
is an AC ground/neutral bond in the main utility breaker panel and that no other ground/neutral bonds exist in the system.
Lightning protection
To protect the equipment from lightning damage, use a
Recommended | Xantrex recommends that if the inverter is more than 8 feet from the |
additional | utility ground rod, a second ground rod should be added (Reference NEC |
grounding | 250.56) and bonded to the same point (Reference NEC 250.58) to |
| minimize the impedance to ground and maximize system protection. |