![ZH078 (6.5 Ton) (Continued)](/images/new-backgrounds/35089/3508945x1.webp)
ZH078 (6.5 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 75.4 | 7.9 | 27.1 | 25.6 | 18.6 | - | - | - | 68.5 | 8.9 | 27.1 | 21.3 | 16.5 | - | - | - |
1625 |
| 72 | 68.0 | 7.6 | 43.7 | 36.6 | 29.6 | 22.5 | - | - | 61.5 | 8.4 | 40.8 | 34.0 | 27.2 | 20.4 | - | - |
| 67 | 60.5 | 7.3 | 60.2 | 47.6 | 40.6 | 33.5 | 26.5 | - | 54.6 | 8.0 | 54.6 | 44.8 | 38.0 | 31.2 | 24.4 | - | |
|
| |||||||||||||||||
|
| 62 | 56.4 | 7.2 | 56.4 | 56.4 | 45.8 | 38.8 | 31.8 | 24.7 | 50.6 | 8.0 | 50.6 | 50.6 | 40.7 | 33.9 | 27.1 | 20.3 |
|
| 77 | 77.4 | 7.9 | 37.5 | 29.1 | 20.6 | - | - | - | 70.2 | 8.9 | 38.3 | 26.7 | 18.4 | - | - | - |
|
| 72 | 69.7 | 7.6 | 49.7 | 41.2 | 32.8 | 24.3 | - | - | 63.0 | 8.5 | 47.1 | 38.7 | 30.3 | 21.9 | - | - |
1950 |
| 67 | 62.1 | 7.3 | 61.9 | 53.4 | 45.0 | 36.5 | 28.0 | - | 55.9 | 8.0 | 55.9 | 50.7 | 42.3 | 33.9 | 25.5 | - |
|
| 62 | 57.8 | 7.3 | 57.8 | 57.8 | 50.8 | 42.4 | 33.9 | 25.4 | 51.8 | 8.0 | 51.8 | 51.8 | 45.4 | 37.0 | 28.6 | 20.3 |
|
| 57 | 61.0 | 7.2 | 61.0 | 59.0 | 50.6 | 42.1 | 33.6 | 25.2 | 55.4 | 7.9 | 55.4 | 53.3 | 44.9 | 36.5 | 28.2 | 19.8 |
|
| 77 | 79.3 | 7.9 | 47.9 | 32.5 | 22.6 | - | - | - | 71.9 | 9.0 | 49.4 | 32.1 | 20.2 | - | - | - |
|
| 72 | 71.5 | 7.6 | 55.8 | 45.9 | 36.0 | 26.1 | - | - | 64.5 | 8.5 | 53.3 | 43.4 | 33.4 | 23.5 | - | - |
2275 |
| 67 | 63.7 | 7.3 | 63.6 | 59.3 | 49.4 | 39.5 | 29.6 | - | 57.2 | 8.0 | 57.2 | 56.5 | 46.6 | 36.7 | 26.7 | - |
|
| 62 | 59.3 | 7.3 | 59.3 | 59.3 | 55.8 | 45.9 | 36.0 | 26.2 | 53.1 | 8.0 | 53.1 | 53.1 | 50.0 | 40.1 | 30.2 | 20.2 |
|
| 57 | 62.6 | 7.2 | 62.6 | 61.6 | 55.5 | 45.6 | 35.8 | 25.9 | 56.7 | 8.0 | 56.7 | 55.7 | 49.5 | 39.6 | 29.6 | 19.7 |
|
| 77 | 81.3 | 8.0 | 58.4 | 35.9 | 24.6 | - | - | - | 73.5 | 9.0 | 60.5 | 37.5 | 22.1 | - | - | - |
|
| 72 | 73.3 | 7.6 | 61.8 | 50.5 | 39.2 | 27.9 | - | - | 66.0 | 8.5 | 59.5 | 48.0 | 36.5 | 25.0 | - | - |
2600 |
| 67 | 65.3 | 7.3 | 65.3 | 65.1 | 53.8 | 42.5 | 31.2 | - | 58.5 | 8.0 | 58.5 | 58.5 | 50.9 | 39.4 | 27.9 | - |
|
| 62 | 60.8 | 7.3 | 60.8 | 60.8 | 60.8 | 49.5 | 38.2 | 26.9 | 54.3 | 8.0 | 54.3 | 54.3 | 54.3 | 43.2 | 31.7 | 20.2 |
|
| 57 | 64.1 | 7.3 | 64.1 | 64.1 | 60.5 | 49.2 | 37.9 | 26.6 | 58.1 | 8.0 | 58.1 | 58.1 | 54.1 | 42.6 | 31.1 | 19.6 |
|
| 72 | 74.2 | 7.6 | 66.7 | 54.3 | 42.0 | 29.7 | - | - | 66.5 | 8.5 | 64.0 | 51.5 | 39.1 | 26.6 | - | - |
2925 |
| 67 | 66.1 | 7.3 | 66.1 | 66.0 | 57.6 | 45.3 | 33.0 | - | 59.0 | 8.0 | 59.0 | 59.0 | 54.5 | 42.0 | 29.6 | - |
| 62 | 61.5 | 7.3 | 61.5 | 61.5 | 61.5 | 49.2 | 36.9 | 24.6 | 54.7 | 8.0 | 54.7 | 54.7 | 54.7 | 42.4 | 30.0 | 17.5 | |
|
| |||||||||||||||||
|
| 57 | 64.9 | 7.3 | 64.9 | 64.9 | 63.1 | 50.8 | 38.4 | 26.1 | 58.5 | 8.0 | 58.5 | 58.5 | 56.5 | 44.1 | 31.6 | 19.2 |
|
| 72 | 75.1 | 7.6 | 71.5 | 58.2 | 44.8 | 31.5 | - | - | 67.0 | 8.5 | 67.0 | 55.1 | 41.6 | 28.2 | - | - |
3250 |
| 67 | 66.9 | 7.3 | 66.9 | 66.9 | 61.5 | 48.1 | 34.8 | - | 59.4 | 8.0 | 59.4 | 59.4 | 58.1 | 44.7 | 31.2 | - |
| 62 | 62.3 | 7.3 | 62.3 | 62.3 | 62.3 | 48.9 | 35.6 | 22.2 | 55.1 | 8.0 | 55.1 | 55.1 | 55.1 | 41.7 | 28.3 | 14.9 | |
|
| |||||||||||||||||
|
| 57 | 65.7 | 7.3 | 65.7 | 65.7 | 65.7 | 52.4 | 39.0 | 25.7 | 58.9 | 8.0 | 58.9 | 58.9 | 58.9 | 45.5 | 32.1 | 18.7 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products | 23 |