XP120 (10 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 111.3 | 11.5 | 44.2 | 37.9 | 28.1 | - | - | - | 102.2 | 12.7 | 45.2 | 30.9 | 25.1 | - | - | - |
2500 |
| 72 | 101.2 | 11.4 | 67.7 | 56.3 | 44.9 | 33.6 | - | - | 92.5 | 12.6 | 64.0 | 52.7 | 41.5 | 30.2 | - | - |
| 67 | 91.1 | 11.3 | 91.1 | 74.8 | 61.8 | 50.4 | 39.1 | - | 82.8 | 12.5 | 82.8 | 71.8 | 57.9 | 46.6 | 35.3 | - | |
|
| |||||||||||||||||
|
| 62 | 85.0 | 11.2 | 85.0 | 85.0 | 67.1 | 55.8 | 44.4 | 33.0 | 77.0 | 12.4 | 77.0 | 77.0 | 58.9 | 47.6 | 36.3 | 25.1 |
|
| 77 | 115.3 | 11.6 | 62.3 | 45.5 | 31.7 | - | - | - | 105.5 | 12.8 | 65.3 | 42.7 | 28.6 | - | - | - |
|
| 72 | 104.9 | 11.5 | 78.4 | 64.5 | 50.7 | 36.8 | - | - | 95.5 | 12.7 | 75.4 | 61.3 | 47.2 | 33.1 | - | - |
3000 |
| 67 | 94.4 | 11.4 | 94.4 | 83.5 | 69.7 | 55.8 | 42.0 | - | 85.5 | 12.6 | 85.5 | 80.0 | 65.9 | 51.8 | 37.7 | - |
|
| 62 | 88.1 | 11.3 | 88.1 | 88.1 | 75.7 | 61.9 | 48.0 | 34.2 | 79.5 | 12.5 | 79.5 | 79.5 | 67.2 | 53.1 | 39.0 | 24.9 |
|
| 57 | 87.1 | 11.4 | 87.1 | 87.1 | 76.5 | 62.7 | 48.8 | 35.0 | 78.6 | 12.5 | 78.6 | 78.6 | 68.4 | 54.3 | 40.2 | 26.1 |
|
| 77 | 119.4 | 11.7 | 80.3 | 53.2 | 35.3 | - | - | - | 108.8 | 12.9 | 85.4 | 54.4 | 32.1 | - | - | - |
|
| 72 | 108.5 | 11.6 | 89.0 | 72.7 | 56.4 | 40.1 | - | - | 98.5 | 12.8 | 86.8 | 69.9 | 53.0 | 36.1 | - | - |
3500 |
| 67 | 97.7 | 11.5 | 97.7 | 92.3 | 77.6 | 61.3 | 45.0 | - | 88.1 | 12.7 | 88.1 | 88.1 | 73.9 | 57.0 | 40.1 | - |
|
| 62 | 91.2 | 11.4 | 91.2 | 91.2 | 84.3 | 68.0 | 51.6 | 35.3 | 82.0 | 12.6 | 82.0 | 82.0 | 75.5 | 58.6 | 41.7 | 24.8 |
|
| 57 | 90.1 | 11.5 | 90.1 | 90.1 | 85.2 | 68.9 | 52.6 | 36.3 | 81.1 | 12.7 | 81.1 | 81.1 | 76.8 | 59.9 | 43.0 | 26.1 |
|
| 77 | 123.4 | 11.8 | 98.4 | 60.8 | 38.9 | - | - | - | 112.1 | 13.0 | 105.5 | 66.1 | 35.6 | - | - | - |
|
| 72 | 112.2 | 11.7 | 99.7 | 80.9 | 62.2 | 43.4 | - | - | 101.5 | 12.9 | 98.2 | 78.5 | 58.8 | 39.0 | - | - |
4000 |
| 67 | 101.0 | 11.6 | 101.0 | 101.0 | 85.5 | 66.7 | 47.9 | - | 90.8 | 12.9 | 90.8 | 90.8 | 81.9 | 62.2 | 42.5 | - |
|
| 62 | 94.2 | 11.5 | 94.2 | 94.2 | 92.8 | 74.1 | 55.3 | 36.5 | 84.4 | 12.7 | 84.4 | 84.4 | 83.7 | 64.0 | 44.3 | 24.6 |
|
| 57 | 93.2 | 11.5 | 93.2 | 93.2 | 93.8 | 75.1 | 56.3 | 37.5 | 83.6 | 12.8 | 83.6 | 83.6 | 83.6 | 65.5 | 45.8 | 26.1 |
|
| 72 | 113.4 | 11.7 | 105.0 | 85.4 | 65.8 | 46.3 | - | - | 102.1 | 12.9 | 102.1 | 82.4 | 62.1 | 41.7 | - | - |
4500 |
| 67 | 102.1 | 11.6 | 102.1 | 102.1 | 90.5 | 70.9 | 51.4 | - | 91.4 | 12.8 | 91.4 | 91.4 | 86.5 | 66.2 | 45.9 | - |
| 62 | 95.3 | 11.5 | 95.3 | 95.3 | 94.6 | 75.0 | 55.4 | 35.8 | 84.9 | 12.7 | 84.9 | 84.9 | 84.6 | 64.3 | 44.0 | 23.7 | |
|
| |||||||||||||||||
|
| 57 | 94.2 | 11.5 | 94.2 | 94.2 | 94.5 | 74.9 | 55.4 | 35.8 | 84.0 | 12.7 | 84.0 | 84.0 | 84.0 | 64.6 | 44.3 | 23.9 |
|
| 72 | 114.6 | 11.6 | 110.3 | 89.9 | 69.5 | 49.1 | - | - | 102.7 | 12.8 | 102.7 | 86.3 | 65.4 | 44.4 | - | - |
5000 |
| 67 | 103.2 | 11.5 | 103.2 | 103.2 | 95.6 | 75.2 | 54.8 | - | 91.9 | 12.7 | 91.9 | 91.9 | 91.1 | 70.2 | 49.3 | - |
| 62 | 96.3 | 11.4 | 96.3 | 96.3 | 96.3 | 75.9 | 55.5 | 35.1 | 85.4 | 12.6 | 85.4 | 85.4 | 85.4 | 64.5 | 43.6 | 22.7 | |
|
| |||||||||||||||||
|
| 57 | 95.2 | 11.5 | 95.2 | 95.2 | 95.2 | 74.8 | 54.4 | 34.0 | 84.5 | 12.7 | 84.5 | 84.5 | 84.5 | 63.6 | 42.7 | 21.8 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products | 59 |