XP090 (7.5 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 88.3 | 9.2 | 32.2 | 27.8 | 20.0 | - | - | - | 80.3 | 10.2 | 26.0 | 24.0 | 16.6 | - | - | - |
1875 |
| 72 | 81.1 | 9.1 | 49.8 | 41.9 | 34.1 | 26.3 | - | - | 73.8 | 10.1 | 46.1 | 38.5 | 30.9 | 23.3 | - | - |
| 67 | 74.0 | 9.1 | 67.3 | 56.1 | 48.2 | 40.4 | 32.6 | - | 67.3 | 10.0 | 65.7 | 52.7 | 45.1 | 37.5 | 29.9 | - | |
|
| |||||||||||||||||
|
| 62 | 69.6 | 9.0 | 69.6 | 69.6 | 57.9 | 50.1 | 42.3 | 34.5 | 64.5 | 10.0 | 64.5 | 64.5 | 53.2 | 45.6 | 38.0 | 30.4 |
|
| 77 | 89.8 | 9.3 | 39.9 | 30.9 | 21.9 | - | - | - | 81.1 | 10.2 | 35.8 | 27.1 | 18.3 | - | - | - |
|
| 72 | 82.6 | 9.2 | 55.3 | 46.4 | 37.4 | 28.4 | - | - | 74.5 | 10.1 | 51.5 | 42.7 | 34.0 | 25.2 | - | - |
2250 |
| 67 | 75.3 | 9.1 | 70.8 | 61.8 | 52.9 | 43.9 | 34.9 | - | 68.0 | 10.0 | 67.2 | 58.4 | 49.6 | 40.9 | 32.1 | - |
|
| 62 | 70.8 | 9.1 | 70.8 | 70.8 | 63.4 | 54.5 | 45.5 | 36.5 | 65.2 | 10.0 | 65.2 | 65.2 | 58.6 | 49.9 | 41.1 | 32.3 |
|
| 57 | 70.3 | 9.1 | 70.3 | 70.3 | 63.9 | 54.9 | 46.0 | 37.0 | 64.5 | 10.0 | 64.5 | 64.5 | 58.1 | 49.4 | 40.6 | 31.8 |
|
| 77 | 91.4 | 9.3 | 47.5 | 34.0 | 23.8 | - | - | - | 81.9 | 10.2 | 45.6 | 30.2 | 20.0 | - | - | - |
|
| 72 | 84.0 | 9.2 | 60.9 | 50.8 | 40.6 | 30.5 | - | - | 75.3 | 10.1 | 56.9 | 47.0 | 37.1 | 27.2 | - | - |
2625 |
| 67 | 76.6 | 9.1 | 74.3 | 67.6 | 57.5 | 47.3 | 37.2 | - | 68.7 | 10.1 | 68.7 | 64.1 | 54.2 | 44.3 | 34.3 | - |
|
| 62 | 72.0 | 9.1 | 72.0 | 72.0 | 69.0 | 58.8 | 48.7 | 38.5 | 65.9 | 10.0 | 65.9 | 65.9 | 64.0 | 54.1 | 44.1 | 34.2 |
|
| 57 | 71.5 | 9.1 | 71.5 | 71.5 | 69.5 | 59.4 | 49.2 | 39.1 | 65.2 | 10.0 | 65.2 | 65.2 | 63.5 | 53.6 | 43.6 | 33.7 |
|
| 77 | 92.9 | 9.3 | 55.1 | 37.0 | 25.7 | - | - | - | 82.7 | 10.2 | 55.4 | 33.3 | 21.7 | - | - | - |
|
| 72 | 85.4 | 9.2 | 66.5 | 55.2 | 43.9 | 32.6 | - | - | 76.0 | 10.2 | 62.4 | 51.3 | 40.2 | 29.1 | - | - |
3000 |
| 67 | 77.9 | 9.2 | 77.9 | 73.4 | 62.1 | 50.8 | 39.5 | - | 69.3 | 10.1 | 69.3 | 69.3 | 58.7 | 47.7 | 36.6 | - |
|
| 62 | 73.3 | 9.1 | 73.3 | 73.3 | 74.5 | 63.2 | 51.9 | 40.6 | 66.5 | 10.1 | 66.5 | 66.5 | 66.5 | 58.3 | 47.2 | 36.1 |
|
| 57 | 72.7 | 9.1 | 72.7 | 72.7 | 75.1 | 63.8 | 52.5 | 41.2 | 65.9 | 10.0 | 65.9 | 65.9 | 65.9 | 57.7 | 46.7 | 35.6 |
|
| 72 | 85.2 | 9.2 | 71.0 | 58.8 | 46.6 | 34.5 | - | - | 75.5 | 10.2 | 66.4 | 54.5 | 42.6 | 30.7 | - | - |
3375 |
| 67 | 77.7 | 9.2 | 77.7 | 75.4 | 65.9 | 53.8 | 41.6 | - | 68.9 | 10.1 | 68.9 | 68.9 | 62.2 | 50.3 | 38.4 | - |
| 62 | 73.1 | 9.1 | 73.1 | 73.1 | 73.7 | 61.5 | 49.3 | 37.1 | 66.1 | 10.1 | 66.1 | 66.1 | 66.1 | 55.6 | 43.7 | 31.8 | |
|
| |||||||||||||||||
|
| 57 | 72.6 | 9.1 | 72.6 | 72.6 | 73.7 | 61.5 | 49.4 | 37.2 | 65.4 | 10.1 | 65.4 | 65.4 | 65.4 | 55.0 | 43.1 | 31.2 |
|
| 72 | 85.0 | 9.3 | 75.5 | 62.4 | 49.4 | 36.3 | - | - | 75.0 | 10.2 | 70.4 | 57.7 | 45.0 | 32.3 | - | - |
3750 |
| 67 | 77.5 | 9.2 | 77.5 | 77.5 | 69.8 | 56.7 | 43.7 | - | 68.4 | 10.1 | 68.4 | 68.4 | 65.7 | 53.0 | 40.3 | - |
| 62 | 72.9 | 9.1 | 72.9 | 72.9 | 72.9 | 59.8 | 46.8 | 33.7 | 65.6 | 10.1 | 65.6 | 65.6 | 65.6 | 52.9 | 40.2 | 27.5 | |
|
| |||||||||||||||||
|
| 57 | 72.4 | 9.1 | 72.4 | 72.4 | 72.4 | 59.3 | 46.2 | 33.2 | 65.0 | 10.1 | 65.0 | 65.0 | 65.0 | 52.3 | 39.6 | 26.9 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.