XP120 (10 Ton) Side Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 |
| 1.6 |
| 1.8 |
| 2.0 |
| ||||||||
(CFM) |
|
|
|
| |||||||||||||||||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | ||||||
| |||||||||||||||||||||
|
| 2 HP & Field Supplied Drive |
|
|
|
| Standard 2 HP & Drive |
|
|
| Hi Static 3 HP & Drive | ||||||||||
2600 | 646 | 0.41 | 698 | 0.62 | 748 | 0.82 | 797 | 1.02 | 844 | 1.21 | 890 | 1.39 | 936 | 1.57 | 980 | 1.74 | 1023 | 1.92 | 1065 | 2.09 | |
2800 | 654 | 0.50 | 706 | 0.71 | 756 | 0.92 | 805 | 1.11 | 852 | 1.30 | 898 | 1.48 | 943 | 1.66 | 987 | 1.83 | 1031 | 2.01 | 1073 | 2.18 | |
3000 | 663 | 0.60 | 714 | 0.81 | 765 | 1.02 | 813 | 1.21 | 861 | 1.40 | 907 | 1.58 | 952 | 1.76 | 996 | 1.93 | 1039 | 2.11 | 1082 | 2.28 | |
3200 | 673 | 0.71 | 724 | 0.93 | 774 | 1.13 | 823 | 1.32 | 871 | 1.51 | 917 | 1.69 | 962 | 1.87 | 1006 | 2.05 | 1049 | 2.22 | 1091 | 2.39 | |
3400 | 684 | 0.84 | 735 | 1.05 | 785 | 1.25 | 834 | 1.45 | 882 | 1.63 | 928 | 1.82 | 973 | 2.00 | 1017 | 2.17 | 1060 | 2.34 | 1102 | 2.52 | |
3600 | 696 | 0.98 | 747 | 1.19 | 798 | 1.39 | 846 | 1.59 | 894 | 1.78 | 940 | 1.96 | 985 | 2.14 | 1029 | 2.31 | 1072 | 2.48 | 1115 | 2.66 | |
3800 | 709 | 1.14 | 761 | 1.35 | 811 | 1.55 | 860 | 1.75 | 907 | 1.93 | 953 | 2.12 | 999 | 2.29 | 1043 | 2.47 | 1086 | 2.64 | 1128 | 2.81 | |
4000 | 724 | 1.31 | 776 | 1.52 | 826 | 1.72 | 874 | 1.92 | 922 | 2.11 | 968 | 2.29 | 1013 | 2.47 | 1057 | 2.64 | 1100 | 2.82 | 1143 | 2.99 | |
4200 | 740 | 1.50 | 792 | 1.71 | 842 | 1.92 | 890 | 2.11 | 938 | 2.30 | 984 | 2.48 | 1029 | 2.66 | 1073 | 2.83 | 1116 | 3.01 | 1159 | 3.18 | |
4400 | 757 | 1.71 | 809 | 1.92 | 859 | 2.13 | 908 | 2.32 | 955 | 2.51 | 1001 | 2.69 | 1046 | 2.87 | 1091 | 3.04 | 1134 | 3.22 | 1176 | 3.39 | |
4600 | 776 | 1.94 | 827 | 2.15 | 877 | 2.35 | 926 | 2.55 | 974 | 2.74 | 1020 | 2.92 | 1065 | 3.10 | 1109 | 3.27 | 1152 | 3.45 | - | - | |
4800 | 795 | 2.19 | 847 | 2.40 | 897 | 2.60 | 946 | 2.79 | 993 | 2.98 | 1040 | 3.16 | 1085 | 3.34 | - | - | - | - | - | - | |
5000 | 816 | 2.45 | 868 | 2.66 | 918 | 2.86 | 967 | 3.06 | 1014 | 3.25 | 1061 | 3.43 | - | - | - | - | - | - | - | - | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3 HP & Field Supplied Drive |
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
XP150 (12.5 Ton) Side Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 |
| 1.6 | 1.8 | 2.0 | |||||||||||
(CFM) |
| ||||||||||||||||||||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM | BHP | RPM | BHP | RPM | BHP | |||
| |||||||||||||||||||||
|
|
|
| 3 HP & Field Supplied Drive |
|
|
|
|
|
| Standard 3 HP & Drive |
|
|
| |||||||
3200 | 673 | 0.71 | 724 | 0.93 | 774 | 1.13 | 823 | 1.32 | 871 | 1.51 | 917 | 1.69 | 962 | 1.87 | 1006 | 2.05 | 1049 | 2.22 | 1091 | 2.39 | |
3400 | 684 | 0.84 | 735 | 1.05 | 785 | 1.25 | 834 | 1.45 | 882 | 1.63 | 928 | 1.82 | 973 | 2.00 | 1017 | 2.17 | 1060 | 2.34 | 1102 | 2.52 | |
3600 | 696 | 0.98 | 747 | 1.19 | 798 | 1.39 | 846 | 1.59 | 894 | 1.78 | 940 | 1.96 | 985 | 2.14 | 1029 | 2.31 | 1072 | 2.48 | 1115 | 2.66 | |
3800 | 709 | 1.14 | 761 | 1.35 | 811 | 1.55 | 860 | 1.75 | 907 | 1.93 | 953 | 2.12 | 999 | 2.29 | 1043 | 2.47 | 1086 | 2.64 | 1128 | 2.81 | |
4000 | 724 | 1.31 | 776 | 1.52 | 826 | 1.72 | 874 | 1.92 | 922 | 2.11 | 968 | 2.29 | 1013 | 2.47 | 1057 | 2.64 | 1100 | 2.82 | 1143 | 2.99 | |
4200 | 740 | 1.50 | 792 | 1.71 | 842 | 1.92 | 890 | 2.11 | 938 | 2.30 | 984 | 2.48 | 1029 | 2.66 | 1073 | 2.83 | 1116 | 3.01 | 1159 | 3.18 | |
4400 | 757 | 1.71 | 809 | 1.92 | 859 | 2.13 | 908 | 2.32 | 955 | 2.51 | 1001 | 2.69 | 1046 | 2.87 | 1091 | 3.04 | 1134 | 3.22 | 1176 | 3.39 | |
4600 | 776 | 1.94 | 827 | 2.15 | 877 | 2.35 | 926 | 2.55 | 974 | 2.74 | 1020 | 2.92 | 1065 | 3.10 | 1109 | 3.27 | 1152 | 3.45 | 1194 | 3.62 | |
4800 | 795 | 2.19 | 847 | 2.40 | 897 | 2.60 | 946 | 2.79 | 993 | 2.98 | 1040 | 3.16 | 1085 | 3.34 | 1129 | 3.52 | 1172 | 3.69 | 1214 | 3.86 | |
5000 | 816 | 2.45 | 868 | 2.66 | 918 | 2.86 | 967 | 3.06 | 1014 | 3.25 | 1061 | 3.43 | 1106 | 3.61 | 1150 | 3.78 | 1193 | 3.95 | 1235 | 4.13 | |
5200 | 839 | 2.73 | 890 | 2.94 | 940 | 3.14 | 989 | 3.34 | 1037 | 3.53 | 1083 | 3.71 | 1128 | 3.89 | 1172 | 4.06 | 1215 | 4.23 | 1257 | 4.41 | |
5400 | 862 | 3.03 | 914 | 3.24 | 964 | 3.44 | 1012 | 3.64 | 1060 | 3.82 | 1106 | 4.01 | 1151 | 4.18 | 1195 | 4.36 | 1238 | 4.53 | 1281 | 4.70 | |
5600 | 886 | 3.34 | 938 | 3.55 | 988 | 3.76 | 1037 | 3.95 | 1084 | 4.14 | 1131 | 4.32 | 1176 | 4.50 | 1220 | 4.67 | 1263 | 4.85 | 1305 | 5.02 | |
5800 | 912 | 3.67 | 964 | 3.89 | 1014 | 4.09 | 1063 | 4.28 | 1110 | 4.47 | 1156 | 4.65 | 1201 | 4.83 | 1246 | 5.01 | 1289 | 5.18 | 1331 | 5.35 | |
6000 | 939 | 4.02 | 990 | 4.23 | 1041 | 4.44 | 1089 | 4.63 | 1137 | 4.82 | 1183 | 5.00 | 1228 | 5.18 | 1272 | 5.35 | 1315 | 5.53 | 1358 | 5.70 | |
6200 | 967 | 4.39 | 1018 | 4.60 | 1068 | 4.80 | 1117 | 4.99 | 1165 | 5.18 | 1211 | 5.36 | 1256 | 5.54 | 1300 | 5.72 | - | - | - | - | |
|
|
|
|
|
| Hi Static 5 HP & Drive |
|
|
|
|
|
| 5 HP & Field Supplied Drive |
|
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
Johnson Controls Unitary Products | 73 |