York R-410A manual YTG-G-1208, ZH120 10 Ton Side Duct, ZH150 12.5 Ton Side Duct

Models: R-410A

1 128
Download 128 pages 30.42 Kb
Page 65
Image 65
ZH120 (10 Ton) Side Duct

246824-YTG-G-1208

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZH120 (10 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

 

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

2 HP & Field Supplied Drive

 

 

 

Standard 2 HP & Drive

 

 

 

Hi Static 3 HP & Drive

 

2600

675

0.53

726

0.74

776

0.94

824

1.12

870

1.30

914

1.48

957

1.65

1000

1.82

1041

1.99

1082

2.17

2800

686

0.63

738

0.84

787

1.04

835

1.23

881

1.41

925

1.58

969

1.76

1011

1.93

1052

2.10

1093

2.27

3000

699

0.75

750

0.96

800

1.16

847

1.34

893

1.52

938

1.70

981

1.87

1024

2.04

1065

2.21

1106

2.39

3200

713

0.88

764

1.09

814

1.28

861

1.47

907

1.65

952

1.83

995

2.00

1037

2.17

1079

2.34

1119

2.52

3400

728

1.02

779

1.23

829

1.43

877

1.61

923

1.79

967

1.97

1010

2.14

1053

2.31

1094

2.48

1135

2.66

3600

745

1.18

796

1.39

846

1.59

893

1.77

939

1.95

984

2.13

1027

2.30

1069

2.47

1111

2.64

1152

2.82

3800

763

1.36

815

1.57

864

1.76

912

1.95

958

2.13

1002

2.31

1046

2.48

1088

2.65

1129

2.82

1170

3.00

4000

783

1.55

835

1.76

884

1.96

932

2.15

978

2.33

1022

2.50

1066

2.67

1108

2.84

1149

3.02

1190

3.19

4200

805

1.77

856

1.98

906

2.17

953

2.36

999

2.54

1044

2.72

1087

2.89

1129

3.06

1171

3.23

1211

3.41

4400

828

2.00

879

2.21

929

2.41

976

2.59

1022

2.77

1067

2.95

1110

3.12

1152

3.29

-

-

-

-

4600

852

2.25

904

2.46

953

2.66

1001

2.85

1047

3.03

1092

3.20

1135

3.37

-

-

-

-

-

-

4800

879

2.52

930

2.73

980

2.93

1027

3.12

1073

3.30

-

-

-

-

-

-

-

-

-

-

5000

906

2.81

958

3.02

1007

3.22

1055

3.41

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZH150 (12.5 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

 

3 HP & Field

Supplied Drive

 

 

 

 

 

Standard 3 HP & Drive

 

 

 

 

 

3200

713

0.88

764

1.09

814

1.28

861

1.47

907

1.65

952

1.83

995

2.00

1037

2.17

1079

2.34

1119

2.52

3400

728

1.02

779

1.23

829

1.43

877

1.61

923

1.79

967

1.97

1010

2.14

1053

2.31

1094

2.48

1135

2.66

3600

745

1.18

796

1.39

846

1.59

893

1.77

939

1.95

984

2.13

1027

2.30

1069

2.47

1111

2.64

1152

2.82

3800

763

1.36

815

1.57

864

1.76

912

1.95

958

2.13

1002

2.31

1046

2.48

1088

2.65

1129

2.82

1170

3.00

4000

783

1.55

835

1.76

884

1.96

932

2.15

978

2.33

1022

2.50

1066

2.67

1108

2.84

1149

3.02

1190

3.19

4200

805

1.77

856

1.98

906

2.17

953

2.36

999

2.54

1044

2.72

1087

2.89

1129

3.06

1171

3.23

1211

3.41

4400

828

2.00

879

2.21

929

2.41

976

2.59

1022

2.77

1067

2.95

1110

3.12

1152

3.29

1194

3.46

1235

3.64

4600

852

2.25

904

2.46

953

2.66

1001

2.85

1047

3.03

1092

3.20

1135

3.37

1177

3.54

1219

3.72

1259

3.89

4800

879

2.52

930

2.73

980

2.93

1027

3.12

1073

3.30

1118

3.47

1161

3.65

1203

3.82

1245

3.99

1285

4.16

5000

906

2.81

958

3.02

1007

3.22

1055

3.41

1101

3.59

1146

3.76

1189

3.94

1231

4.11

1273

4.28

1313

4.45

5200

936

3.12

987

3.33

1037

3.53

1084

3.72

1130

3.90

1175

4.07

1218

4.24

1260

4.42

1302

4.59

1343

4.76

5400

966

3.45

1018

3.66

1067

3.86

1115

4.05

1161

4.23

1206

4.40

1249

4.57

1291

4.74

1333

4.91

1373

5.09

5600

999

3.80

1050

4.01

1100

4.20

1147

4.39

1193

4.57

1238

4.75

1281

4.92

1323

5.09

1365

5.26

1405

5.44

5800

1032

4.16

1084

4.37

1133

4.57

1181

4.75

1227

4.93

1271

5.11

1315

5.28

1357

5.45

1398

5.62

-

-

6000

1067

4.54

1119

4.75

1168

4.95

1216

5.13

1262

5.31

1306

5.49

1350

5.66

-

-

-

-

-

-

6200

1103

4.94

1155

5.15

1204

5.34

1252

5.53

1298

5.71

-

-

-

-

-

-

-

-

-

-

 

 

 

Hi Static 5 HP & Drive

 

 

 

 

 

 

5 HP & Field Supplied Drive

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

Johnson Controls Unitary Products

65

Page 65
Image 65
York R-410A manual YTG-G-1208, ZH120 10 Ton Side Duct, ZH150 12.5 Ton Side Duct, Johnson Controls Unitary Products